ABB i-bus KNX Product Manual page 223

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Group objects
No.
76
This group object is enabled if the parameter Setpoint specification and adjustment is set to Absolute and the parameter
Comfort heating setpoint = Comfort cooling setpoint is set to No in the Setpoint manager parameter window.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Comfort heating. The value received via this
group object is permanently stored and serves as the new Comfort heating setpoint. Manual setpoint adjustment acts on this
setpoint.
The value must lie in the valid value range of 10...40 °C. A value outside this range is limited to this range.
76
This group object is enabled if the parameter Setpoint specification and adjustment is set to Absolute and the parameter
Comfort heating setpoint = Comfort cooling setpoint is set to Yes in the Setpoint manager parameter window.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Comfort heating and cooling. The value received
via this group object is permanently stored and serves as the new Comfort heating and cooling setpoint. Manual setpoint
adjustment acts on this setpoint.
The value must lie in the valid value range of 10...40 °C. A value outside this range is limited to this range.
77
This group object is enabled if the parameter Setpoint specification and adjustment is set to Absolute and the parameter
Comfort heating setpoint = Comfort cooling setpoint is set to no in the Setpoint manager parameter window.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Comfort cooling. The value received via this
group object is permanently stored and serves as the new Comfort cooling setpoint. Manual setpoint adjustment acts on this
setpoint.
The value must lie in the valid value range of 10...40 °C. A value outside this range is limited to this range.
78
This group object is enabled if the parameter Setpoint specification and adjustment in the Setpoint manager parameter
window is parametrized with Absolute.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Economy heating. The value received via this
group object is permanently stored and serves as the new Economy heating setpoint. Manual setpoint adjustment acts on this
setpoint.
The value must lie in the valid value range of 10...40 °C. A value outside this range is limited to this range.
The value must be less than the value for comfort heating. If a value is not below this value, the device will automatically
classify it below this value.
Object function
Comfort heating setpoint
Setpoint for Comfort heating and cooling
Comfort cooling setpoint
Economy heating setpoint
Name
Channel A – Controller
Channel A – Controller
Channel A – Controller
Channel A – Controller
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 221
Data type
Flags
2 bytes
C, W
DPT 9.001
2 bytes
C, W
DPT 9.001
2 bytes
C, W
DPT 9.001
2 bytes
C, W
DPT 9.001

Advertisement