ABB i-bus KNX Product Manual page 164

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.9.4.3
Dependent parameter
Send group object "Status Valve purge"
Options:
This parameter defines when the Status Valve purge group object is to be sent.
No, update only: With this option only the object value for the group object is updated, however this
value is not sent over the bus.
On request: The valve purging status value is sent on the receipt of a command via the Request
status values group object.
After a change: The value is sent on a change in the object value (e.g. change from 0 to 1).
Cyclically: If this option is selected, the status value is sent automatically after an adjustable time has
elapsed. Displays the dependent parameter All.
After a change or request: The status is sent on request and on a change.
After a change or request and cyclically: The status is sent on request and on a change and cyclically.
Displays the dependent parameter All.
7.9.4.3.1
Dependent parameter
Every
Options:
This parameter is used to set the time after which the status values are to be sent cyclically. The group
objects are sent after each cycle.
162 2CDC508220D0211 Rev. A | VC/S 4.x.1
No, update only
After a change
Cyclically
On request
After a change or on request
After a change or request and cyclically
00:00:30...00:05:00...18:12:15 hh:mm:ss