KNX
Group objects
No.
79
This group object is enabled if the parameter Setpoint specification and adjustment in the Setpoint manager parameter
window is parametrized with Absolute.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Economy cooling. The value received via this
group object is permanently stored and serves as the new Economy cooling setpoint. Manual setpoint adjustment acts on this
setpoint.
The value must lie in the valid value range of 10...40 °C. A value outside this range is limited to this range.
The value must be greater than the value for comfort cooling. If a value is not below this value, the device will automatically
classify it below this value.
80
This group object is enabled if the parameter Setpoint specification and adjustment in the Setpoint manager parameter
window is parametrized with Absolute.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Standby heating. The value received via this
group object is permanently stored and serves as the new Standby heating setpoint. Manual setpoint adjustment acts on this
setpoint.
The value must lie in the valid value range of 10...40 °C. A value outside this range is limited to this range.
The value must be less than the value for comfort heating. If a value is not below this value, the device will automatically
classify it below this value.
81
This group object is enabled if the parameter Setpoint specification and adjustment in the Setpoint manager parameter
window is parametrized with Absolute.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Standby cooling. The value received via this
group object is permanently stored and serves as the new Standby cooling setpoint. Manual setpoint adjustment acts on this
setpoint.
The value must lie in the valid value range of 10...40 °C. A value outside this range is limited to this range.
The value must be greater than the value for comfort cooling. If a value is not below this value, the device will automatically
classify it below this value.
82
This group object is enabled if the parameter Setpoint specification and adjustment in the Setpoint manager parameter
window is parametrized with Absolute.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for building protection heating (frost protection).
The value received via this group object is permanently stored and serves as the new building protection heating setpoint.
Manual setpoint adjustment acts on this setpoint.
The value must lie in the valid value range of 5...15 °C. A value outside this range is limited to this range.
The value must be less than the value for comfort heating. If a value is not below this value, the device will automatically
classify it below this value.
222 2CDC508220D0211 Rev. A | VC/S 4.x.1
Object function
Economy cooling setpoint
Standby heating setpoint
Standby cooling setpoint
Building Protection heating setpoint
Name
Channel A – Controller
Channel A – Controller
Channel A – Controller
Channel A – Controller
Data type
Flags
2 bytes
C, W
DPT 9.001
2 bytes
C, W
DPT 9.001
2 bytes
C, W
DPT 9.001
2 bytes
C, W
DPT 9.001