ABB i-bus KNX Product Manual page 150

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.8.2.1.2.1
Dependent parameter
Time interval for cyclical monitoring
Options:
The monitoring time within which the group object must be received is specified using this parameter.
Otherwise the Error: operating mode receipt alarm object is changed to alarm and the value set in the
Operating mode after exceeding monitoring time parameter applies.
7.8.2.1.2.2
Dependent parameter
Operating mode after exceeding monitoring time
Options:
The selection made here defines which operating mode is to apply on the erroneous reception of the
Operating mode group object. This mode remains active until a new value is received in the group object
monitored.
7.8.2.1.3
Dependent parameter
Monitor receipt of group object "Heating/cooling changeover"
The parameter is only visible if in the Heating/cooling changeover parameter in the Application parameters
parameter window, the Only via object or Via slave and via object option has been selected.
Options:
The monitoring of the Heating/cooling changeover group object is enabled using this parameter.
The change in the type of operation can be monitored using this parameter.
Deactivated: The monitoring of the Heating/cooling changeover group object is deactivated.
Activated: The monitoring of the group object is active. The dependent parameters Time interval for
cyclical monitoring and Heating/cooling mode when monitoring time exceeded as well as the
Error: heating/cooling receipt group object are enabled.
148 2CDC508220D0211 Rev. A | VC/S 4.x.1
00:00:30...00:05:00...18:12:15 hh:mm:ss
Building Protection
Comfort
Standby
Economy
Deactivated