ABB i-bus
KNX
Parameters
7.8.2.1.2.1
—
Dependent parameter
Time interval for cyclical monitoring
Options:
The monitoring time within which the group object must be received is specified using this parameter.
Otherwise the Error: operating mode receipt alarm object is changed to alarm and the value set in the
Operating mode after exceeding monitoring time parameter applies.
7.8.2.1.2.2
—
Dependent parameter
Operating mode after exceeding monitoring time
Options:
The selection made here defines which operating mode is to apply on the erroneous reception of the
Operating mode group object. This mode remains active until a new value is received in the group object
monitored.
7.8.2.1.3
—
Dependent parameter
Monitor receipt of group object "Heating/cooling changeover"
The parameter is only visible if in the Heating/cooling changeover parameter in the Application parameters
parameter window, the Only via object or Via slave and via object option has been selected.
Options:
The monitoring of the Heating/cooling changeover group object is enabled using this parameter.
The change in the type of operation can be monitored using this parameter.
•
Deactivated: The monitoring of the Heating/cooling changeover group object is deactivated.
•
Activated: The monitoring of the group object is active. The dependent parameters Time interval for
cyclical monitoring and Heating/cooling mode when monitoring time exceeded as well as the
Error: heating/cooling receipt group object are enabled.
148 2CDC508220D0211 Rev. A | VC/S 4.x.1
00:00:30...00:05:00...18:12:15 hh:mm:ss
Building Protection
Comfort
Standby
Economy
Deactivated
Activated