ABB i-bus KNX Product Manual page 91

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.6.7.1.1.2
Dependent parameter
Extended settings
Options:
Extended settings can be enabled using this parameter. This parameter is displayed on the selection of
the Yes option.
Dependent parameter
Hysteresis
Options:
This parameter is used to specify the hysteresis that is to apply to the setpoint to prevent continuous
switching of the controller.
Upper switching point = setpoint + hysteresis
Lower switching point = setpoint – hysteresis
Heating controller:
If the actual temperature is below the lower switching point, the controller switches on.
If the actual temperature is above the upper switching point, the controller switches off.
Cooling controller:
If the actual temperature is below the lower switching point, the controller switches off.
If the actual temperature is above the upper switching point, the controller switches on.
No
Yes
0.0...0.5...25.5
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 89