KNX
Parameters
7.8.2.1.5
Dependent parameter
Monitor receipt of group object "Window contact"
This parameter is only visible if the Channel function parameter has been parameterized with the
Controller channel option.
This parameter is only visible if the Via group object option has been selected for the Window status input
parameter in the Application parameters parameter window.
Options:
The monitoring of the Window contact group object is activated using this parameter. The regular
reception of the window status can be monitored using this parameter.
Deactivated: The monitoring of the Window contact group object is deactivated.
Activated: The monitoring of the group object is active. The dependent parameter Time interval for
cyclical monitoring and the Error: window contact receipt group object are enabled.
7.8.2.1.5.1
Dependent parameter
Time interval for cyclical monitoring
Options:
The monitoring time within which the group object must be received is specified using this parameter.
Otherwise the Error: window contact receipt alarm object is changed to alarm and the controller reacts as
if the window were open. This means that the controller changes over to the Building Protection mode.
This mode remains active until a new value is received in the group object monitored.
Deactivated
Activated
00:00:30...00:05:00...18:12:15 hh:mm:ss