ABB i-bus KNX Product Manual page 62

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.4.1.5
Dependent parameter
Fill level sensor input
This parameter is not visible if the Channel function parameter has been parameterized with the Actuator
channel option.
This parameter is not visible if the Basic-stage cooling parameter is deactivated.
Options:
This parameter is used to inform the integrated controller whether it is to include the level in
a condensation tray (Alarm/No alarm) in the control.
Deactivated: If Deactivated has been selected, the level alarm is not taken into account by
the controller.
Via physical device input: If this option is selected, the controller checks which of the physical device
inputs has been parameterized for a fill level sensor. The status of the fill level sensor connected to
this input is included in the control. The message: Configure in 'Inputs' parameter window appears.
Only device inputs that have been parameterized as a fill level sensor are detected as such.
If no input has been parameterized as a fill level sensor, the function is considered deactivated.
If several inputs have been parameterized as a fill level sensor, there is a logical OR link between these
inputs. As soon as one of the contacts signals the status "Fill level reached", the controller evaluates the
status as "Fill level alarm". Conversely, if none of the inputs signals the status "Fill level reached",
the controller evaluates the status as "No fill level alarm".
Via group object: The fill level alarm is received via a group object. The dependent Fill level alarm
group object appears. The fill level alarm must be connected to the group object using this object.
In addition, the dependent Fill level reached when parameter is enabled.
60 2CDC508220D0211 Rev. A | VC/S 4.x.1
Deactivated
Via physical device input
Via group object
Note