ABB i-bus KNX Product Manual page 191

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Dependent parameter
Activate minimum signal duration
Options:
Dependent parameter
When contact opens
Options:
Dependent parameter
When contact closes
Options:
What is minimum signal duration?
In contrast to the maximum dead time, a telegram only sent once the minimum signal duration has
elapsed.
In more detail:
If an edge is detected on the input, the minimum signal duration starts to run. No telegrams are sent on the
bus at this time. The signal on the input is observed for the minimum signal duration. If a further edge
appears at the input during the minimum signal duration, it is interpreted as a new operation, and the
minimum signal duration restarts. If no further edges occur after the minimum signal duration starts,
a telegram is sent on the bus after it has elapsed.
No
Yes
0...1...100 s
0...1...100 s
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 189