Dimensions Of Flue Gas Outlet Pipe - REMEHA Gas 120 ACE Series Installation And Service Manual

Floor-standing condensing gas boiler
Hide thumbs Also See for Gas 120 ACE Series:
Table of Contents

Advertisement

5 Installation
Configura­
Description
tion
C
Concentric pipes in the boiler
93
room
C
93X
Single flexible pipes in the chim­
ney (combustion air in counter-
current)
C
Concentric pipes in the boiler
93
room
C
93X
Single flexible pipes in the chim­
ney (combustion air in counter-
current)
Tab.23
PPS pipe reduction for each element used
Diameter
45° elbow
87° elbow
Straight inspection tube
87° inspection elbow
Inspection T
Inspection tube for flexible pipe
Fig.23
Dimensions of open connection
ød
1
Fig.24
Dimensions of parallel connection
ød
1
34
Gas 120 ACE
Materials
PPS
PPS
80 mm
Single
1.2 m
1.9 m
0.3 m
1.9 m
4.2 m
0.3 m
5.7.3
d
Tab.24
80 mm
100 mm
150 mm
AD-3001094-01
d
D
Tab.25
80/80 mm
100/100 mm
110/110 mm
150/150 mm
øD
1
AD-3000963-01
Diameter
80/125 mm
80 mm
110/150 mm
110 mm
80/125 mm
Concentric
1.0 m
1.5 m
0.6 m
2.0 m
2.7 m
-

Dimensions of flue gas outlet pipe

Warning
The pipes connected to the flue gas adapter must satisfy the
following dimension requirements.
External dimensions of flue gas outlet pipe
1
Dimensions of pipe
d
(min-max)
1
79.3 - 80.3 mm
99.3 - 100.3 mm
149 - 151 mm
External dimensions of flue gas outlet pipe
1
External dimensions of air supply pipe
1
Dimensions of pipe
d
(min-max)
1
79.3 - 80.3 mm
99.3 - 100.3 mm
109.3 - 110.3 mm
149 - 151 mm
Gas 120
Gas 120
ACE - 65
ACE - 90
-
-
16.5
13.5
100 mm
100/150 mm
Single
Concentric
1.1 m
1.0 m
2.0 m
3.7 m
-
1.0 m
4.8 m
5.6 m
2.5 m
0.5 m
D
(min-max)
1
79.3 - 80.3 mm
99.3 - 100.3 mm
109.3 - 110.3 mm
149 - 151 mm
7717202 - v03 - 24062019
Gas 120
ACE - 115
-
9.4
-
-