Allen-Bradley PowerFlex 700AFE Migration Manual page 39

Regenerative bus supply
Hide thumbs Also See for PowerFlex 700AFE:
Table of Contents

Advertisement

Table 13 - Protection Features (Continued)
Description
PowerFlex 700AFE Bus Supply
Cat No. 20Y...
Single Phase/
(s)
Phase Loss Fault
Line Sync Fault
(s)
Input Overcurrent Fault
(s)
Overload Fault
(s)
IGBT Over temp Fault
(s)
LCL Filter Over temp Fault
(s)
DC Bus Over Voltage Fault
(s)
DC Bus Under Voltage
(s)
AC Line Fuse Blown Fault
DC Bus Fuse Blown Fault
Precharge Fault
AC Input Over Voltage Fault
Cooling Fan Fault/Alarm
(s)
Transient Voltage Suppressor
(TVSS) Fail Alarm
DC Bus Conditioner Fault
(o) external device
Table 14 - User Interface
Description
PowerFlex 700AFE Bus Supply
Cat No. 20Y...
Local HIM
(o) 20-HIM-A3, 20-HIM-A6
Remote HIM
(o) 20-HIM-C3S, 20-HIM-C6S
DriveExplorer/DriveExecutive (s)
Connected Components
(s)
Workbench (CCW)
Studio5000/RSLogix 5000
(s) with communication option
Digital Inputs
(s) 6, 24V DC
• inputs 1...5 used for door
• input 6 used for Hardware Enable
Digital Outputs
(s) 2, form C relay, outputs 1, 2 used
for door-mounted operator devices.
• Relay 240V AC/30V DC 1200VA,
Rockwell Automation Publication 750-RM003A-EN-P - April 2018
PowerFlex 755TM Bus Supply
Cat. No. 20J...
(s)
(s)
(s)
(s)
(s)
(s)
(s)
(s)
(s)
(s)
(s)
(s)
(s)
(s)
(s)
PowerFlex 755TM Bus Supply
Cat. No. 20J...
(o) 20-HIM-A6
(o) 20-HIM-C6S
(s)
(s)
(o) 20-750 series 24V DC and 115V AC I/O
modules;
controls
3...6, depending on option module
chosen
(o) 20-750 series 24V DC and 115V AC I/O
modules;
2...3, relay or transistor depending on
150 W resistive or, 240V AC/
option module chosen.
30V DC, 840VA, 105 W inductive.
• Relay NO, 240V AC/24V DC, 2 A
• Relay NC, 240V AC/24V DC, 2 A resistive.
• Transistor, 24V DC, 1 A max resistive.
Selection Considerations
Chapter 1
resistive/general purpose inductive.
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerflex 755tm

Table of Contents