PowerFlex 755TM Common Bus Inverter ND Rating
400V, 50 Hz Input
Code
Amps
kW
302
302
160
367
367
200
460
460
250
540
540
315
585
585
315
650
650
355
750
750
400
770
770
400
920
920
500
1K0
1040
560
1K1
1112
630
1K2
1175
710
1K4
1465
800
1K6
1590
850
1K7
1715
1000
2K1
2156
1250
2K8
2849
1650
3K5
3542
2000
f11
PowerFlex 755TM Common Bus Inverter ND Rating
600V, 60 Hz Input
Code
Amps
Hp
242
242
250
295
295
300
355
355
350
395
395
400
435
435
450
545
545
550
595
580
600
690
690
700
760
760
800
825
825
900
980
980
1000
1K1
1045
1100
1K2
1220
1250
1K5
1430
1500
2K0
1946
2000
2K4
2420
2500
7
8...10
11
12
F
2K3
M
N
e
f9...f12
g
h
PowerFlex 755TM Common Bus Inverter ND Rating
Frame
Code
302
361
430
505
8
545
617
710
740
800
960
9
1K0
1K1
1K3
1K4
10
1K6
2K0
11
2K6
12
3K4
PowerFlex 755TM Common Bus Inverter ND Rating
Frame
Code
215
265
330
8
370
415
505
565
650
9
735
820
920
1K0
10
1K1
1K4
11
1K8
12
2K3
Rockwell Automation Publication 750-RM003A-EN-P - April 2018
13
14
15
16
17
D
N
N
N
N
i
Positions 14...18 are not used.
f10
480V, 60 Hz Input
Amps
Hp
Frame
302
250
361
300
430
350
505
400
8
545
450
617
500
710
600
740
650
800
700
960
800
1045
900
9
1135
1000
1365
1100
1420
1250
1655
1500
10
2072
1800
2738
2400
11
3404
3000
12
f12
690V, 50 Hz Input
Amps
kW
Frame
215
200
265
250
330
315
8
370
355
415
400
505
500
565
560
650
630
735
710
9
820
800
920
900
1030
1000
1150
1100
10
1419
1400
1865
1800
11
2318
2300
12
Selection Considerations
18
N
-C0-C11-P15...
Control and Power Options
g
Filtering and CM Cap Configuration
(1)
Code
EMC Filtering
PE-A
PE-B
J
Yes
Installed
Removed
K
Yes
Installed
Removed
L
No
Installed
Removed
M
No
Installed
Removed
(1) Setting does not apply to product type 20G with input types
D and E. PE-A jumpers are removed when bus conditioner
for marine applications (-P51) is selected.
h
(1)
Dynamic Braking
Code
Internal Resistor
Internal Transistor
N
No
(1) Not available on Frames 8...12, specify Code 'N' .
i
Door-mounted HIM (Frames 8...10)
Code
Operator Interface and Control
No Door-mounted HIM
A
with TotalFORCE Control
Enhanced LCD, Full Numeric, IP66, NEMA Type 4X/12 with
D
TotalFORCE Control
20G Control Options Selection
Code
Option
Frames
C0
Torque Accuracy Module
8...12
(1)
C11
Single Pod (with Control Bay)
8...12
(1)
C12
Dual Pod (with Control Bay)
8...12
(1) When code 'D' is selected in position 13, code C11 includes
one door-mounted HIM and code C12 includes two door-
mounted HIMs.
20J Control Options Selection
Code
Option
Frames
Control Transformer
C1
8...12
(1)
(Internal 240V)
(1) This option only applies to 755TM regenerative and low
harmonic bus supplies. If this option is not selected, a 240V
AC, single-phase, neutral grounded external power source
must be supplied by the customer.
20G Power Options Selection
Code
Option
Frames
P15
Top Cable Exit w/wiring bay
8...12
P16
Top Cable Entry w/wiring bay
10...12
P17
Top Cable Entry no wiring bay
8... 9
P46
System DC Bus (4700 Amp)
8...10
P50
DC Bus Conditioner
8...12
DC Bus Conditioner – Marine
P51
8...12
Applications
20J Power Options Selection
Code
Option
Frames
P16
Top Cable Entry w/wiring bay
10...12
P17
Top Cable Entry no wiring bay
8... 9
P46
System DC Bus (4700 Amp)
8...10
P50
DC Bus Conditioner
8...12
DC Bus Conditioner – Marine
P51
8...12
Applications
Chapter 1
Reflected Wave
Filtering
No
Yes
No
Yes
No
Input Type
D, E, F, G
D, E
D, E
Input Type
F
Input Type
D, E, F, G
F, G
F, G
D, E
F, G
F, G
Input Type
F
F
F
F
F
19