Allen-Bradley PowerFlex 700AFE Migration Manual page 51

Regenerative bus supply
Hide thumbs Also See for PowerFlex 700AFE:
Table of Contents

Advertisement

Figure 7 - PowerFlex 700AFE Main Control Board I/O Slots and Jumper Locations
J5
J4
J3
J2
J1
1
2
3
Table 24 - PowerFlex 700AFE Main Control Board I/O and Jumper Locations
No.
Description
1
Analog I/O signals
2
24V DC Digital Inputs
3
Relay Digital Outputs
J1
Analog In 1 voltage/current select
J2
Analog In 2 voltage/current select
J3
Analog Out 1 voltage/current select
J4
Analog Out 2 voltage/current select
J5
Hardware Enable
See the PowerFlex 700AFE User Manual, publication
connector wiring and analog configuration jumpers.
See
Hardware Enable Circuits on page 55
Hardware Enable.
ATTENTION: Digital Inputs 1, 3, 4, and 5, and Digital Outputs 1 and 2 are
factory-wired and programmed to operate from the controls on the front of
the enclosure door. Do not change the wiring and programming for those
digital inputs and outputs, or the system will malfunction.
IMPORTANT If the existing PowerFlex 700AFE system uses any of the available analog I/O,
you need to supply and configure an appropriate PowerFlex 750 I/O option
module for the replacement PowerFlex 755TM bus supply. See
more details.
Rockwell Automation Publication 750-RM003A-EN-P - April 2018
Selection Considerations
20Y-UM001
for I/O
for information on how to use