Regenerative bus supply
Hide thumbs Also See for PowerFlex 700AFE:
Table of Contents

Advertisement

No clearance is required between the back of the enclosure and a wall.
PowerFlex 755T products can be mounted on a service pad or platform. The
platform height and enclosure setback measurements that are indicated in
Figure 33
are the maximum that is allowed for by the PowerFlex 750-Series
service cart (20-750-MCART1). The platform height measurement is also an
installation limit per NEC requirements for the disconnect switch.
Figure 33 - Mounting Clearances for IGBT Access and Disconnect Switch Height
Side View
Maximum Enclosure Setback
Side View
20-750-MCART1
Rockwell Automation Publication 750-RM003A-EN-P - April 2018
203 mm
(8 in.)
254 mm
Maximum Platform or
(10 in.)
Plinth System Height
Minimum Aisle Width
914 mm
(36 in.)
Enclosure Information
Appendix A
Side View
Top View
152 mm
(6 in.)
97