Allen-Bradley PowerFlex 700AFE Migration Manual page 58

Regenerative bus supply
Hide thumbs Also See for PowerFlex 700AFE:
Table of Contents

Advertisement

Chapter 1
Selection Considerations
2
1
Item
Name
1
Input power terminals
L1, L2, L3
2
SHLD terminal, line PE,
ground
3
SHLD terminal, motor
PE, ground
4
DC bus
(1) Maximum/minimum sizes that the terminals can accept. These sizes are not recommendations.
(2) Do not exceed maximum wire size. Parallel connections can be required.
(3) These connections are bus bar type terminations and require the use of lug type connectors.
(4) Apply counter-torque to the nut on the other side of terminations when tightening or loosening the terminal bolt to avoid damage to the terminal.
58
Figure 11 - PowerFlex 700AFE Frame 13 IP20 MCC Power Terminal Locations
Front View
Table 29 - PowerFlex 700AFE Frame 13 IP21 Rittal Power Terminal Specifications
Frame
Description
13
Input power
(1)
(3)
13
Terminating point for wiring shields
(3)
(3)
(DC–, DC+)
13
DC output (using cable)
DC output (using right-side splice kit
SK-Y1-BUSSPLICE-F13R)
DC output (using left-side splice kit
SK-Y1-BUSSPLICE-F13L)
Rockwell Automation Publication 750-RM003A-EN-P - April 2018
Shown with
enclosure doors
and side removed.
3
Right Side View
(1) (2)
Wire Size Range
Torque
Max
Min
Recommended
2
2
380 mm
53 mm
50 N•m
(750 MCM)
(1/O AWG)
(442 lb•in)
2
2
300 mm
2.1 mm
40 N•m
(600 MCM)
(14 AWG)
(354 lb•in)
2
2
380 mm
2.1 mm
70 N•m
(750 MCM)
(14 AWG)
(620 lb•in)
40 N•m
(354 lb•in)
4
Terminal Bolt
(3) (4)
Size
M5-M10
M12
M10