Bus Bar Connections
AC line input power and output motor cables with appropriate barrel lugs are
connected directly to bus bars and use the fastening hardware provided. Keep
the wire connections at least 51 mm (2 in.) away from the ends of the extruded
bus bar. Clamp kits, SK-RM-GRNDCLMP-nn, are available for making
connections to the PE ground bar.
Figure 14 - Bus Bar Connections
51 mm
(2 in.)
Frame 8 Cable Connections
Customer-supplied M12 hardware.
Rockwell Automation Publication 750-RM003A-EN-P - April 2018
Selection Considerations
51 mm
(2 in.)
38.0 N•m (336 lb•in)
M10: 15 mm
M12: 19 mm
Ground Clamp
Chapter 1
61