Heater Disconnection Alarm [ Hb-A ] - Autonics DPU Series User Manual

1-phase digital thyristor unit
Hide thumbs Also See for DPU Series:
Table of Contents

Advertisement

6. Parameter setting and functions
6.3.7

Heater disconnection alarm [ HB-A ]

When load resistance display method is set as [ UP ], it is over the set value, this alarm occurs.
[ H-BK ] and display value flashes for 2 sec. in turn in the display part and EVT indicator flashes for
0.5 sec.
Even though heater disconnect alarm occurs, control operation continues.
It is cleared automatically when the value is below the SV of heater disconnect alarm value.
(1) Heater disconnection alarm value setting [ HB-V ]
Regardless of control method (phase control, cycle control), it operates. For the operation, over
10% of control output (phase control, cycle control) and over 30% of rated current are required.
• Set range: 10 to 500 (unit: %)
Hysteresis of heater disconnect alarm is fixed as 1% for ON/OFF interval.
When SV for heater disconnect alarm is 50%, alarm turns ON at 50%, alarm turns OFF at 49%.
(2) Heater disconnection alarm delay time [ HB-T ]
When load resistance display method is set as [ DOWN ] and load resistance value is under the SV
of [ HB-V ], alarm disconnection alarm occurs after the set delay time.
• Set range: 0, 1, 2, 3, 5, 10, 20, 30 (unit: sec.)
44
ON
OFF
49%
SV
50%
© Copyright Reserved Autonics Co., Ltd.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Digipower 2000

Table of Contents