6.2.3
Startlimit[ S-LM ]andstartlimittime[ S-LT ]
When power is ON, changing to RUN status from STOP status, or alarm reset, set limit output
value and time to prevent the inrush current or error current.
Output(%)
Start
limit
A: Soft start [ ST-T ] function ends
B: Slow up [ UP-T ] function ends
C: Slow down [ DN-T ] function ends
Regardless of control method setting (phase control or cycle control), it operates as phase control.
• Start limit [ S-LM ] set range: 0 to 110 of output (unit: %)
• Start limit time [ S-LT ] set range: 0 to 100 sec.(unit: sec.)
6.2.4
Outputslopesetting[ SLOP ]
This function is to set output changed ratio by control input from 0.00 to 1.00 range.
Output value when setting slope is input(%) X slope value.
Output(%)
©CopyrightReservedAutonicsCo.,Ltd.
SOFT START set time
Start limit set time
Control input signal(%)
6.Parametersettingandfunctions
SLOW UP set time
Time
SLOW DOWN set time
Output slope
value(%)
33