6.2.7
Slowup/Slowdown
It is same purpose as soft start function.
Soft start starts only one time at first but slow up/slow down function start during operation.
Regardless of control method setting (phase control or cycle control), it operates as phase control.
Output(%)
SOFT START set time
A : Soft start ends, B : Slow up ends, C : Slow down ends
When it reaches to the target output value, slow up/slow down functions end. When it sets as '0',
slow up/slow down do not operate.
• Set range: 0 to 100 (unit: sec.)
6.2.8
Outputhighlimitvalue[ H-OL ],Outputlowlimitvalue[ L-OL ]
This function is to high/low limit output range to protect load.
Output(%)
• Set range: 0 < output low limit value < output high limit value < 100 (unit: %)
©CopyrightReservedAutonicsCo.,Ltd.
SLOW UP set time
Control input signal(%)
6.Parametersettingandfunctions
Time
SLOW DOWN set time
Output high-limit: H-OL
Output low-limit : L-OL