5.Installationandinitialoperation
5.3.4
SettingMode1[ ST-1 ]
RUN
mode
Press
key
for 3 sec.
Operating Mode
Setting Mode 1
OP
Control input type
Control method
DI-1 function
DI-2 function
DI-3 function
Input correction
Input slope correction
Display value content
Bar content
Load resistance
display method
Full load auto recognition
Com. address
Com. speed
Com. write
24
※ 1.
: Press any key among
P
※ If there is no operation any keys in 30sec., it returns to RUN mode.
※ Press the
Press the
※ When setting [ LOCK] as LOC2 or LOC3, and entering ST-1, it displays only [ LOCK] parameter.
: This parameter may or may not appear, depending on the other parameter settings.
ST-1
Displays setting mode 1.
※ 1
P
IN-P
4-20
C-MD
Select control method.
PA
V-FB
DI-1
Select digital input.
※ Multi SP function [ SP-M] is available only in DI-1.
DI-2
SP-M
DI-3
Set input correction value.
IN-B
• Set range : -99.9 to 99.9%
Set input slope correction value.
SPAN
• Set range : -99.9 to 99.9%
DISP
Select display value content.
Select bar graph display content.
BAR
DRES
Select display method of load resistance value.
F-LD
Select full load auto recognition enable/disable.
Set communication address.
ADDR
• Set range : 1 to 99
Select communication speed
BAUD
(baud rate).
Select communication write enable/disable.
COMW
(ENA: Enables to write, DISA: Disables to write)
Lock
LOCK
Select lock function.
,
.
key when entering ST-1 setting mode in any parameters, it moves to ST-1.
key once more, it returns to RUN mode.
Select input type.
C-FB
W-FB
SP-1
SP-2
LD-V
V
※ Displayed only for RS485 communication option model.
48
OFF
LOC1
F-CY
V-CY
SP-3
RST
HOLD
AMP
KW
A
KW
DOWN
UP
OFF
ON
96
192
ENA
DISA
LOC2
LOC3
©CopyrightReservedAutonicsCo.,Ltd.
ONOF
REF
REF
384