5.3.5

Setting Mode 2[ ST-2 ]

RUN
mode
Press
key
for 3 sec.
Operating Mode
Setting Mode 1
OP
ST-1
© Copyright Reserved Autonics Co., Ltd.
※ 1.
: Press any key among
P
※ If there is no operation any keys in 30sec., it returns to RUN mode.
※ Press the
key when entering ST-2 setting mode in any parameters, it moves to ST-2.
Press the
key once more, it returns to RUN mode.
※ When setting [ LOCK] as LOC2 or LOC3, and entering ST-2, it displays only [ LOCK] parameter.
Setting Mode 2
ST-2
Displays setting mode 2.
Overcurrent
※ 1
alarm value
P
OC-V
Overcurrent
delay time
Set alarm delay time for overcurrent.
OC-T
• Set range : 0 to 100sec
Overcurrent alarm CH
OC-A
Overvoltage
alarm value
Select alarm value for overvoltage.
OV-V
• Set range : 0 to 120%
Overvoltage delay time
Set alarm delay time for overvoltage.
OV-T
• Set range : 0 to 100sec
Overvoltage alarm CH
OV-A
Fuse break
alarm CH
FUSE
Heat sink overheating
alarm CH
HEAT
Element error
alarm CH
SCR
Heater disconnect
alarm value
Set alarm value for heater disconnection.
HB-V
• Set range : 10 to 500%
Heater disconnect
alarm CH
HB-A
Select heater disconnect alarm channel.
NON
Heater disconnect
alarm delay time
HB-T
Set heater disconnect alarm delay time.
• Set range : 0, 1, 2, 3, 5, 10, 20, 30 sec.
5. Installation and initial operation
,
.
Set alarm value for overcurrent.
120
• Set range : 0 to 120%
Select overcurrent channel.
NON
AL1
Select each alarm channel.
NON
AL1
AL1
AL2
AL2
AL2
25