Typical Power Cable Sizes, Iec - ABB ACH580-01 Hardware Manual

Table of Contents

Advertisement

Typical power cable sizes, IEC

The table below gives copper cable types with concentric copper shield for the drives
with nominal current. The value separated by the plus sign means the diameter of the
PE conductor.
See page
280
for the cable lead-through sizes allowed for the selected drive frame
size.
IEC
type
ACH580-01-
3-phase U
= 230 V
N
04A7-2
06A7-2
07A6-2
12A0-2
018A-2
025A-2
032A-2
047A-2
060A-2
089A-2
115A-2
144A-2
171A-2
213A-2
276A-2
3-phase U
= 400 V
N
02A7-4
03A4-4
04A1-4
05A7-4
07A3-4
09A5-4
12A7-4
018A-4
026A-4
033A-4
039A-4
046A-4
062A-4
073A-4
-
088A-4
106A-4
145A-4
169A-4
206A-4
246A-4
Guidelines for planning the electrical installation 97
Frame
Cu cable type
size
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×2.5 + 2.5
R2
3×4.0 + 4.0
R2
3×6.0 + 6.0
R3
3×10 + 10
R3
3×10 + 10
R5
3×35 + 16
R5
3×50 + 25
R6
3×70 + 35
R7
3×95 + 50
R7
3×120 + 70
R8
2×(3×70 + 35)
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×2.5 + 2.5
R1
3×2.5 + 2.5
R2
3×2.5 + 2.5
R2
3×6 + 6
R3
3×10 + 10
R3
3×10 + 10
R3
3×10 + 10
R4
3×25 + 16
R4
3×35 + 16
R4
R5
3×50 + 25
R5
3×70 + 35
R6
3×95 + 50
R7
3×120 + 70
R7
3×150 + 70
R8
2×(3×70+35)
1)
AI cable type
2
mm
3×50 + 25
3×70 + 35
3×120 + 70
3×150 + 70
3×240 + 120
2×(3×95 + 50)
-
1,2)
2
mm
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ACH580-01 and is the answer not in the manual?

Table of Contents

Save PDF