Iec Ratings At Un = 480 V - ABB ACH580-01 Hardware Manual

Table of Contents

Advertisement

IEC ratings at U
Type
Input
ACH580
rating
-01-
I
1
A
3-phase U
= 480 V
N
02A7-4
2.1
03A4-4
3.0
04A1-4
3.4
05A7-4
4.8
07A3-4
6.0
09A5-4
7.6
12A7-4
11.0
018A-4
14.0
026A-4
21.0
033A-4
27.0
039A-4
34.0
046A-4
40.0
062A-4
52
073A-4
65
088A-4
77
106A-4
96
145A-4
124
169A-4
156
206A-4
180
246A-4
240
293A-4
260
363A-4
361
430A-4
414
Definitions
U
Nominal output voltage of the drive. For input voltage range U
N
Electrical power network specification
I
Nominal input current. Continuous rms input current (for dimensioning cables
1
and fuses).
I
Maximum output current. Available for two seconds at start.
max
I
Nominal output current. Maximum continuous rms output current allowed (no
N
overload). This is indicated in the type designation label as output current I2.
P
Nominal power of the drive. Typical motor power (no overload). The kilowatt
N
ratings apply to most IEC 4-pole motors. The horsepower (hp) ratings apply to
most NEMA 4-pole motors.
I
Maximum current with 10% overload, allowed for one minute every ten minutes
Ld
P
Typical motor power in light-duty use (10% overload). The horsepower (hp)
Ld
ratings apply to most NEMA 4-pole motors.
= 480 V
N
Output ratings
Max.
Nominal use
current
I
I
max
Ld
A
A
2.9
2.1
3.8
3.0
5.4
3.5
6.1
4.8
7.2
6.0
8.6
7.6
13.7
12.0
19.8
14.0
25.2
23.0
37.8
27.0
48.6
34.0
61.2
44.0
76
52
104
65
122
77
148
96
178
124
247
156
287
180
350
240
418
260
542
361
542
414
Heat
dissipation
P
Ld
hp
W
1.0
45
1.5
55
2.0
66
3.0
84
3.0
106
5.0
133
7.5
174
10.0
228
15.0
322
20.0
430
25.0
525
30.0
619
40
835
50
1024
60
1240
75
1510
100
1476
125
1976
150
2346
200
3336
200
3936
300
4836
350
6036
on page 286.
Technical data 247
Air flow
Frame
size
3
m
/h
43
R1
43
R1
43
R1
43
R1
43
R1
43
R1
43
R1
101
R2
101
R2
179
R3
179
R3
179
R3
134
R4
134
R4
139
R5
139
R5
435
R6
450
R7
450
R7
550
R8
550
R8
1150
R9
1150
R9
3AXD00000586715.xls L
, see section
1

Advertisement

Table of Contents
loading

Table of Contents