Cable type
PE
A single-core cable system: three
phase conductors and PE conductor
on cable tray
L1
L2
L2
L3
L3
L1
Preferable cable arrangement to
avoid voltage or current unbalance
between the phases
Not allowed power cable types
Cable type
Symmetrical shielded cable with
individual shields for each phase
conductor

Additional guidelines, North America

Follow these additional guidelines for North America with the general guidelines in
section
General guidelines, IEC and North America
ABB recommends the use of conduit for power wiring to the drive and between the
drive and the motor(s). Due to the variety of application needs, metallic and non-
metallic conduit can be used. ABB prefers the use of metallic conduit. Where
permitted, non-metallic conduit may be used.
The following tables show examples of various materials and methods for wiring the
drive in the intended application. See NEC 70 along with state and local codes for the
appropriate materials for your application.
Guidelines for planning the electrical installation 93
Use as input power
high-power input power
cables in an IT network,
make sure that the non-
conductive outer sheath
(jacket) of the cables have
L3
good contact with a
L1
L2
properly grounded
conductive surface, for
example, install the cables
on a properly grounded
cable tray. Otherwise
voltage may become
present on the non-
conductive outer sheath of
the cables, and there is
even a risk of an electric
Use as input power
PE
cabling
Yes
WARNING! If you
use unshielded
shock.
cabling
No
on page 89.
Use as motor cabling
No
Use as motor cabling
No