Ul (Nec) Ratings At Un = 208/230 V - ABB ACH580-01 Hardware Manual

Table of Contents

Advertisement

UL (NEC) ratings at U
Type
Input
ACH580
rating
-01-
I
1
A
3-phase U
= 200...240 V, P
1
04A6-2
4.6
06A6-2
6.6
07A5-2
7.5
10A6-2
10.6
017A-2
16.7
024A-2
24
031A-2
31
046A-2
46
059A-2
59
075A-2
75
088A-2
88
114A-2
114
143A-2
143
169A-2
169
211A-2
211
273A-2
273
See definitions and notes on page 251.
= 208/230 V
N
Output ratings
Max.
Light-duty use
current
I
I
max
Ld
A
A
at U
= 208/230 V, 60 Hz
n
N
6.3
4.6
8.9
6.6
11.9
7.5
14.3
10.6
22.6
16.7
32.7
24.2
43.6
30.8
62.4
46.2
83.2
59.4
107
74.8
135
88
158
114
205
143
257
169
304
211
380
273
Heat
dissipation
P
Ld
hp
BTU/h
W
1.0
155
45
1.5
187
55
2.0
224
66
3.0
288
84
5.0
454
133
7.5
593
174
10
777
228
15
1100
322
20
1469
430
25
1791
525
30
2114
619
40
2852
835
50
3535
1035
60
4272
1251
75
5194
1521
100
7039
2061
Technical data 249
Air flow
Frame
size
CFM
25
R1
25
R1
25
R1
25
R1
25
R1
59
R2
59
R2
105
R3
105
R3
170
R4
82
R5
82
R5
256
R6
265
R7
265
R7
324
R8
3AXD00000586715.xls L