To verify configuration, the user must first be connected to the Rosemount 3095FB using the
Rosemount FB user interface software.
3095FB User Interface Software Packages
• Part Number 03095-5130-0003: Windows User Interface Software–Single PC License,
Converter, and Cable.
• Part Number 03095-5125-0004: Windows User Interface Software–Single PC License.
• Part Number 03095-5125-0005: Windows User Interface Software– Site License.
• Part Number 03095-5106-0002: RS-485 Converter and Cable.
Verify Tag Information
1. Click Transmitter on the taskbar.
2. Click Device Info... from the drop-down menu.
3. Verify tag information.
4. Click OK to exit.
Verify Damping
1. Click Transmitter on the taskbar.
2. Click Damping... from the drop-down menu.
3. Verify damping settings for DP, SP, and PT.
4. Click OK to exit.
Verify Units of Measure
1. Click Transmitter on the taskbar.
2. Click on Units... from the drop-down menu.
3. Verify units of measure for DP, SP, and PT.
4. Click OK to exit.
Verify Sensor Range
1. Click Transmitter on the taskbar.
2. Click on Sensor Limits... from the drop-down menu.
3. Verify sensor limits.
4. Click Cancel to exit.
10
C
ONFIGURATION
Quick Installation Guide
00825-0100-4738, Rev BA
October 2009