Step 1: Mount the Transmitter
Step 2: Consider Housing Rotation
Step 3: Connect the Wiring and Power Up
Step 4: Verify Configuration
Step 5: Trim the Transmitter
Product Certifications
Rosemount 3095FB
Transmitter

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rosemount 3095FB MultiVariable MODBUS and is the answer not in the manual?

Questions and answers

Summary of Contents for Emerson Rosemount 3095FB MultiVariable MODBUS

  • Page 1 Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009 ™ Rosemount 3095FB MultiVariable Transmitter ® with MODBUS Protocol Step 1: Mount the Transmitter Step 2: Consider Housing Rotation Step 3: Connect the Wiring and Power Up Step 4: Verify Configuration Step 5: Trim the Transmitter Product Certifications ®...
  • Page 2: Important Notice

    October 2009 © 2009 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. Emerson Process Management GmbH & Co. OHG Rosemount Inc. 8200 Market Boulevard Argelsrieder Feld 3...
  • Page 3: Step 1: Mount The Transmitter

    Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009 1: M OUNT THE RANSMITTER Liquid Flow Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward.
  • Page 4 Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009 2: C ONSIDER OUSING OTATION Consider Housing Rotation To improve field access or to better view the optional LCD display: 1. Loosen the housing rotation set screw. 2. Rotate the housing clockwise to the desired position – up to 180° from its original position. Over rotating will damage the transmitter.
  • Page 5 Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009 CONTINUED 3. Connect the transmitter to the process. 4. Install the RTD Cable Assembly (optional). All RTD 3095 Cable Assemblies use the 3095 RTD Cable Connector. Identify the cable type being installed and follow the steps below.
  • Page 6 Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009 CONTINUED • Installing a Shielded 3095 RTD Cable (See Figure 4) Note: Shielded cable is intended for use in a conduit. a.Fully engage the black cable connector to the 3095 RTD Connector. b.Tighten the cable adapter until metal contacts metal.
  • Page 7: Bolting Considerations

    Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 6 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
  • Page 8 Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009 CONTINUED Figure 7. Torque values for the flange and flange adapter bolts Bolt Material Head Markings Initial Torque Final Torque Carbon Steel (CS) 300 in.-lbs. 650 in.-lbs. Stainless Steel (SST) 150 in.-lbs.
  • Page 9: Step 3: Connect The Wiring And Power Up

    Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009 3: C ONNECT THE IRING AND OWER Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked FIELD TERMINALS. 2. Connect the lead from the positive power supply terminal to the “+” terminal (PWR/COMM) and the lead from the negative power supply terminal to the “–”...
  • Page 10: Step 4: Verify Configuration

    Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009 4: V ERIFY ONFIGURATION To verify configuration, the user must first be connected to the Rosemount 3095FB using the Rosemount FB user interface software. 3095FB User Interface Software Packages • Part Number 03095-5130-0003: Windows User Interface Software–Single PC License, Converter, and Cable.
  • Page 11: Step 5: Trim The Transmitter

    RIM THE RANSMITTER NOTE Transmitters are shipped from Emerson Process Management, Rosemount Division fully calibrated per request or by the factory default of full scale. Zero Offset Trim A zero trim is a single-point adjustment used for compensating mounting position effects.
  • Page 12: Product Certifications

    Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office. ATEX Directive (94/9/EC) Emerson Process Management complies with the ATEX Directive. European Pressure Equipment Directive (PED) (97/23/EC) 3095F_2/3,4/D Flow Transmitters —...
  • Page 13: European Certifications

    Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009 Canadian Standards Association (CSA) Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/III, Division 1, Groups E, F, and G, hazardous locations. CSA enclosure Type 4X.
  • Page 14 Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009...
  • Page 15 Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009...
  • Page 16 Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009...
  • Page 17 Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009...
  • Page 18 Quick Installation Guide 00825-0100-4738, Rev BA Rosemount 3095FB October 2009...

Table of Contents