Installer Setup
Cycles Per Hour
The Cycles Per Hour setting may limit the number of times per hour your
HVAC unit may energize. For example, at a setting of 6 cycles per hour the
HVAC unit will only be allowed to energize once every 10 minutes. The
Cycles Per Hour limit may be overridden and reset by pressing the UP or
DOWN buttons on the thermostat. Settings are No Limit, 2, 3, 4, 5, or 6.
Compressor Minimum Off Minutes
This feature allows the user to set a minimum off time for the compressor.
Settings are 5 mins., 3 mins., or 0 mins.
Minimum Heat/Cool Setpoint Difference
This feature allows the user to set the minimum gap between Heat and
Cool setpoints in AUTO mode. Select from 0 to 6. If setup step 2 is not set
for AUTO-CHANGEOVER, this step will not appear.
Number of Compressor Stages
This feature is for heat pump applications only.
This feature allows the thermostat to control 1 or 2 compressor stages
when configured for heat pump.
Wired Sensor Use
This feature allows the user to choose if the wired sensor will be used
as an indoor or outdoor sensor.
Control To Temp Source
This feature allows the user to specify which temperature sensor source
the thermostat will use to measure room temperature. The choices are:
Thermostat: Uses the internal thermostat sensor only.
Remote Sensor: Uses wireless or wired sensors only.
NOTE: If a remote sensor is being used, the degree icon on the large room
temperature display will blink.