Electrical rating:
Temperature control range: 55°F to 90°F (13°C to 32°C)
Accuracy: ± 1°F (± 0.5°C)
System configurations: 2-stage heat, 2-stage cool
Timing:
Anti-short Cycle: 4 minutes (bypass anti-short cycle delay by returning to OFF mode for 5 seconds)
Backlight Operation: 10 seconds
Terminations: A, L, S1, S2, R, C, W1, Y1, W2, Y2, G, O
Always turn off power at the main power supply before installing, cleaning, or removing thermostat.
Package includes: 910121748 thermostat on base, thermostat cover, wiring labels, screws and wall anchors, Installation, Operation and Application Guide
Tools required for installation: Drill with 3/16" bit, hammer, screwdriver
ELECTRICAL SHOCK HAZARD – Turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position before removing the existing thermostat.
ELECTRICAL SHOCK HAZARD – Turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position before removing the existing thermostat.
Thermostat installation must conform to local and national building and electrical codes and ordinances.
Note: Mount the thermostat about five feet above the floor. Do not mount the thermostat on an outside wall, in direct sunlight, behind a door, or in an area affected by a vent or duct.
WSHP Main Control Board Terminals TB1 and TB2
Terminals S1 and S2 can be used for an indoor remote sensor.
The indoor remote sensor is used to read the indoor temperature in a different location. This is beneficial when the thermostat is not mounted in the ideal location. The remote sensor P/N is 910116773.
Remote Sensor:
(Contact Daikin for optional remote sensor.)
Note: Remote or outdoor sensor reading can be displayed by simultaneously pressing the Down and SYS buttons.
R – 24 VAC hot
C – 24 VAC common
W 1 – 1st stage heat
Y 1 – 1st stage cool
W 2 – 2nd stage heat
Y 2 – 2nd stage cool
G – Fan
A – Alarm input
L – Status input
O – Override/reset
1ST Cool | 2ND Cool | 1ST Heat | 2ND Heat | |
Heat/Cool | Y1 | YI, Y2 | W1 | W1, W2 |
The 910121748 thermostat is configurable for all systems. The configuration directly affects the outputs.
Use the output chart to correctly configure and wire the thermostat to your system.
The configuration mode is used to set the 910121748 to match your heating/cooling system. To configure the 910121748, perform the following steps:
Press the up or down button to change settings within each screen.
Press the right button to advance to the next screen.
Note: Pressing the left button will return you to the previous screen.
To exit configuration mode, press the CONFIG switch for 1 second.
The setup screens for Configuration Mode are as follows:
Note: If there is no remote sensor, option 1 must be selected.
Press the up or down button to select.
Press the configuration button for two seconds to exit configuration.
The 910121748 is a programmable, manual or auto changeover, 2-stage heat, 2-stage cool thermostat. An outdoor sensor can be used to monitor the outdoor temperature.
The thermostat activates the heating appliance when the room temperature is below the set heat temperature (by the differential temperature). The 910121748 will stop outputting when the call for heat has been satisfied.
When the room temperature is greater than the set cool temperature (by the differential temperature), the cooling device is activated. The 910121748 will stop outputting when the call for cooling is satisfied.
The 910121748 has five possible operating modes: OFF, Heat, Cool, Heat & Cool, and Program mode. In off mode, the thermostat will not turn on heating or cooling devices. The manual fan can be turned on in all operating modes using the fan button. In heat mode, the thermostat controls the heating system. In the cool mode, the thermostat controls the cooling system. In heat & cool mode, the thermostat controls both the heating and cooling systems. In program mode, the thermostat will automatically be controlled by the set program. Program mode can function with heat mode, cool mode, or heat & cool mode. The clock display alternates with the set temperature display for heat & cool mode.
The program schedule can be overridden by changing the set temperature (up or down button). This puts the 910121748 thermostat into a 2-hour temporary hold. After 2 hours, it will automatically return to the program schedule.
The programmable fan feature can be used to recirculate air while in Program mode. It is activated during the program schedule set up.
Pressing the UP and DOWN buttons simultaneously for 2 seconds then releasing them causes the thermostat to output from the "O" terminal for 5 seconds. " Or" will show on the display. This will result in the unit going into a night set-back override.
Pressing the UP and DOWN buttons simultaneously for 5 seconds causes the thermostat to output from the "O" terminal for 10 seconds. " rS" will show on the display. This will result in the unit being reset.
UP – Used to increase the time, set temperatures and to adjust configuration settings.
DOWN – Used to decrease the time, set temperatures and to adjust configuration settings.
SYS (left) – Used to change from OFF, HEAT, COOL and AUTO changeover modes
FAN (right) – Used to turn on and off the indoor fan.
PROG (SYS and FAN) – Used to change from program operation to manual operation.
DOWN and SYS – Pressed simultaneously to display outdoor remote temperature if remote sensor is connected.
UP and DOWN – Used to override night set back or reset the unit.
There are five possible operating modes for the 910121748. Off, Cool, Heat, and Cool & Heat modes are accessed by pressing the SYS (left) button. Program mode is accessed by pressing the SYS (left) and FAN (right) buttons simultaneously.
OFF Mode
Heat Mode
Cool Mode
Cool and Heat Mode (Auto Changeover)
Program Mode
Once the thermostat is configured, it should be thoroughly tested.
Do not energize the air conditioning system when the outdoor temperature is below 50 degrees. It can result in equipment damage or personal injury.
The time and day of the week must be set for your program schedule to operate correctly.
Press the PROG button in for 2 seconds to lock values into memory and return to the OFF mode or press the FAN (right) button once to enter programming.
Program Overview
The 910121748 programmable thermostat has four periods (MORN, DAY, EVE, NITE) that are customizable for each day of the week. Each period will have a start time, heat temperature, cool temperature and programmable fan option. The 910121748 monitors the day and time, while maintaining the specific conditions you have chosen for each period in your program.
Setting the program schedule:
From this screen you have 2 options:
Screen 1 | SUN | MON | TUE | WED | THU | FRI | SAT |
Screen 2 | MON | TUE | WED | THU | FRI | ||
Screen 3 | MON | ||||||
Screen 4 | TUE | ||||||
Screen 5 | WED | ||||||
Screen 6 | THU | ||||||
Screen 7 | FRI | ||||||
Screen 8 | SUN | SAT | |||||
Screen 9 | SAT | ||||||
Screen 10 | SUN |
From any of the screens on above, you can press the FAN (right) button to begin entering your program schedule. The days shown on the display will all be programmed simultaneously.
Once the FAN (right) button is pressed, MORN blinks.
Use the up or down button to select a different period (MORN, DAY, EVE, NITE).
Press FAN (right) button to advance to the next screen. Transition time hour blinks.
Use the up or down button to select a different hour.
Press FAN (right) button to advance to the next screen. Transition time minutes blink.
Use the up or down button to select different minutes.
Press FAN (right) button to advance to the next screen. Heat set temperature displays.
Use the up or down button to adjust the heat set temperature.
Press FAN (right) button to advance to the next screen. Cool set temperature displays.
Use the up or down button to adjust the cool set temperature.
Press FAN (right) button to advance to the next screen. Programmable fan screen displays.
Use the up or down button to select:
Choose:
Off – Programmable fan disabled
On – Indoor fan on continuously
Note: Programmable fan operates in Program mode only.
Repeat above steps to program the four periods per day.
When the program schedule is complete, press and hold the PROG button (SYS and FAN buttons pressed simultaneously) in for 2 seconds to return to the OFF mode.
The 910121748 comes preprogrammed with the following schedule:
MONDAY thru SUNDAY | MORN | 6:00 AM | DAY | 8:00 AM | EVE | 6:00 PM | NITE | 10:00 PM |
HEAT | 70°F | HEAT | 62°F | HEAT | 70°F | HEAT | 62°F | |
COOL | 78°F | COOL | 85°F | COOL | 78°F | COOL | 82°F | |
FAN | Off | FAN | Off | FAN | Off | FAN | Off |
MONDAY thru SUNDAY
MORN | 6:00 AM |
HEAT | 70°F |
COOL | 78°F |
FAN | Off |
DAY | 8:00 AM |
HEAT | 62°F |
COOL | 85°F |
FAN | Off |
EVE | 6:00 PM |
HEAT | 70°F |
COOL | 78°F |
FAN | Off |
NITE | 10:00 PM |
HEAT | 62°F |
COOL | 82°F |
FAN | Off |
Use the following personal program schedule to record your settings:
Symptom | Remedy |
No display | Check for 24 VAC at thermostat; display is blank when 24 VAC is not present Time and day of week must be reset after extended power loss |
All thermostat buttons are inoperative | Verify 24 VAC is present; unit locks out when 24 VAC is not present |
No response with first button press | First button press activates backlight only |
Program schedule activates at the wrong time | Check time (AM/PM) set on thermostat (see Setting the Time) |
Thermostat turns on and off too frequently | Adjust temperature differential (see Configuration Mode Settings 2 & 3) |
Thermostat does not follow program | Verify it is operating in program mode (PROG displays); check time (AM/PM); check if in 2 hour program override |
Fan runs continuously | Press FAN (right) button to turn fan off |
Fan turns on occasionally | Program Mode: Check programmable fan setting in program schedule |
Status indicator on | WSHP status blink code |
Room temperature is not correct | Calibrate thermostat (see Configuration Mode Setting 8) If remote sensor is used, check S1 and S2 terminal connections |
on display instead of room temperature | Check for a bad connection at S1 and S2 terminals, if used (see Configuration Mode Setting 9) |
Heat or Cool not coming on | Verify wiring is correct, gently pull on each wire to verify there is a good connection at terminal block |
Alarm light on | Unit in alarm lockout condition |
Problem not listed above | Press Reset button once* |
* Reset Button Function: Time and day are reset, configuration and program settings are unchanged.
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.DaikinApplied.com or call 800-432-1342. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.DaikinApplied.com.
Daikin Training and Development
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Products manufactured in an ISO certified facility.