Daikin DZK-MTS-3 - Thermostat Manual

Daikin DZK-MTS-3 - Thermostat Manual

Also See for DZK-MTS-3:

Advertisement

Daikin DZK-MTS-3 - Thermostat Manual

ASSEMBLY

ASSEMBLY

FUNCTIONALITIES

FUNCTIONALITIES - Main screen

Meaning Action
1 On/Off On/off for the zone
2 Zone settings Access to zone parameters
3 User settings Access to user settings menu
4 Time schedules Access to time schedules menu
5 Local ventilation Enable / disable the local ventilation
6 Zone demand Displayed when the zone is calling for demand
7 Set-point temperature Change the set-point temperature
8 Room temperature and humidity percentage Displays the room temperature and the relative humidity in the zone
9 Current zone Access to remote zone control
10 Operation mode Access to operation mode menu (Main only)
11 User mode Access to User mode menu (Main only)
12 Airflow control Access to Airflow control menu (Main only)

FUNCTIONALITIES - Idle screen

Meaning Action
1 Date and time Displays the current date and time
2 Current zone Displays the name of the current zone
3 Room temperature Displays the room temperature
4 Humidity percentage Displays the percentage of room humidity
5 On/Off On/off for the zone
6 Operation mode Displays the current operation mode

CONNECTION

Note: Do not connect the "-" pole to the "+" terminal. It may damage the device.
CONNECTION

EXCEPTION CODES

Meaning
Error 1 Communication error with the main controller
Error 5 Temperature sensor is open
Error 6 Temperature sensor is short circuited
Error 8 Wireless Lite thermostat not found
Error 9 Communications error between the Daikin Interface Board and the system
Error 10 Communication error between the DZK BACnet Interface and the system
Error 11 Communication error between the Daikin Interface Board and the Daikin indoor unit

Note: Refer to the DZK installation manual for troubleshooting steps.

WIRED THERMOSTAT

Color graphic interface with capacitive screen for controlling zones in DZK systems. Powered by Main Control Board. Finished in steel and glass.

Functionalities:

  • Available languages: English, French and Spanish.
  • Control of set point temperature. Displayed in 1ºF/0.5ºC increments.
  • Configurable set point range for Cooling and Heating.
  • Auto changeover mode can automatically change to cool/heat mode at set point ±1ºF/0.5ºC (can be configured from 0 to 7ºF using field settings) with a guard timer of 15, 30, 60 or 90 minutes.
  • Room temperature and relative humidity measurement of the zone.
  • Operation mode, user mode and airflow control (Only Main Wired Thermostat).
  • Timer function.
  • Time schedules programming.
  • Remote access to other zones of the system.
  • Configurable as Main or Zone thermostat.

Phone: (855) 770-5678 | http://www.daikinac.com

TECHNICAL SPECS

Power supply and consumption
Type of power supply Vdc
V max 12 V supplied from the Main Control Board
I max 145 mA
Stand-by consumption 0.876 W
Connection and communications
Shielded twisted pair AWG 20 – 4 wired
Maximum wiring length
(Control board to thermostat)
130 ft (40 m)
Operating temperatures
Storage -4 to 158ºF (-20 to 70 ºC)
Operation 32 to 122ºF (0 to 50ºC)
Operating humidity range 5 to 90% (non-condensing)
Set-point temperature range 59 to 86ºF (15 to 30ºC)
Reading accuracy ±1ºF (±0.5 ºC)
Display accuracy ±1ºF (±0.5 ºC)
Relative humidity ±4%
Mechanical aspects
Assembly Surface through support
Protection class IP 20
Type of probe Airzone_NTC_10K
Weight (Mass) 0.44 lb (198 g)
Dimensions (WxHxD) 3.62x3.62x0.62 inch (92x 92x15.85 mm)

Dimensions

Dimensions

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Daikin DZK-MTS-3 - Thermostat Manual

Advertisement

Need Assistance?

Do you have a question about the DZK-MTS-3 that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents