Command Sources (P0700); Off And Brake Function - Siemens MICROMASTER 430 Operating Instructions Manual

7.5kw-90kw 3ac-frequency inverters for controlling the speed of three phase ac motors
Hide thumbs Also See for MICROMASTER 430:
Table of Contents

Advertisement

Issue 05/02
4.2

Command sources (P0700)

ATTENTION
The ramp-up /ramp-down times and ramp smoothing also have an effect on the
motor's start and stop behaviour. Further details about these functions are to be
found in the parameter list for parameters P1120, P1121, P1130 – P1134.
Start motor
Default:
Additional settings:
Stop motor
There are a number of possibilities to stop the motor:
Default :
♦ OFF1
♦ OFF2
♦ OFF3
Additional settings:
Reversing the direction of rotation of the motor
This function is inhibited in the factory settings. To release it, you must set
P1110 = 0.
Default:
Additional settings:
4.3

OFF and brake function

4.3.1
OFF1
This command (which is triggered by the cancellation of the ON order) causes the
inverter to come to a standstill within the selected ramp-down time.
For parameters to change ramp-down time: see P1121
ATTENTION
The ON and the subsequent OFF command must come from the same source.
If the ON / OFF1 command is set for more than one digital input, only the
digital input set last will be valid, e.g. DIN3 is active.
OFF1 can be combined with direct current or compound braking.
MICROMASTER 430
Operating Instructions
6SE6400-5AE00-0BP0
4 MICROMASTER 430 functions
terminal 5 (DIN1, high)
see P0700 to P0708
terminal 5 (DIN1, low)
OFF key on BOP-2, press the OFF key once for 2
seconds or press twice
not active in factory settings
see P0700 to P0708
terminal 6 (DIN2, high)
see P0700 to P0708
51