Installation
4.1
Mounting of the enclosure
Drill the mounting holes according to the mounting template. The polycarbonate enclosure can
also be fixed onto mounting rails, see chapter "14. Spare Parts and Accessories".
Fix the back cover of the enclosure with 4 screws, max. diameter 4.2 mm
scope of supply.
Perform the electrical connection according chapter "6. Electrical connection".
Fix the front cover onto the back cover with the four screws included in the scope of supply.
metal housing
Fig. 1
Mounting of metal and polycarbonate housing
4.2
Connecting the EE07 sensing probes
The humidity (RH) probe or the combined humidity and temperature (RH&T) probe must be
connected at position 1. The T probe must be connected at position 2.
EE220 with fixed probes
position 1
RH probe
∅13
(0.51")
Fig. 2
Connecting the EE07 sensing probes
4.2.1
EE07 probes connected directly to EE220
In order to avoid misreading caused by self-heating, the device shall be installed with the probes
pointing downwards. In very humid, condensing environment it is recommended to use the
EE220 version with remote probe, please see below.
6
EE220 with remote sensing probe
position 2
t probe
∅6
(0.24")
∅12
(0.47")
Operating instructions for EE220 humidity / temperature transmitter
(0.2")
polycarbonate
housing
∅13
(0.51")
position 1
RH/t probe
, not included in the