Fault/Error Messages Via Leds; Error Messages Of The Power Supply Modules; Intf, Dc5V, Dc24V Leds - Siemens Simatic M7-400 Reference Manual

Programmable controllers module specifications
Hide thumbs Also See for Simatic M7-400:
Table of Contents

Advertisement

3.5

Fault/Error Messages via LEDs

Introduction
The power supply modules of the S7-400 indicate module faults and backup
battery faults via LEDs on the front plate.
Overview of the Fault/Error Messages
Table 3-7
Module fault
Backup battery fault
INTF, 5 VDC, 24 VDC
The following table shows the faults indicated by the INTF, 5 VDC, and 24 VDC
LEDs and lists how to remedy the faults.
The status of the BAF, BATTF, BATT1F, and BATT2F LEDs is not relevant here.
Table 3-8

INTF, DC5V, DC24V LEDs

LED
INTF DC5V DC24V
D
D
D
Standby switch in
Line voltage missing
Internal fault, power supply module
defective
Cutoff after overvoltage on 5 V or illegal
external supply
Power supply module operated in
wrong slot
Short circuit or overload on 5 V
D
H
D
Overvoltage on 24 V
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Error messages of the power supply modules

Type of Fault/Error
Cause of Fault
position
Power Supply Modules
LEDs
INTF
5 VDC
24 VDC
Power supplies with 1 backup battery:
BAF
BATTF
Power supplies with 2 backup batteries:
BAF
BATT1F
BATT2F
Remedy
Set standby switch to the
Check line voltage
Replace power supply module
Disconnect from mains and reconnect
after approximately 1 minute; if
necessary, remove external supply
Install the power supply module in the
correct slot (slot 1)
Switch off the power supply module,
remove the source of the short circuit;
after approximately 3 seconds, the
power supply module can be switched
on with the standby switch or via the
power system.*
Check if the supply is external; if not,
replace power supply module
position