Analog Modules
Table 5-10 Analog Value Representation in the Voltage Measuring Ranges ± 500 mV to ± 25 mV
System
Dec.
Hex.
118.515% 32767
7FFF
117.593% 32512
7F00
117.589% 32511
7EFF
27649
6C01
100.000% 27648
6C00
75% 20736
5100
0.003617% 1
1
0% 0
0
–1
FFFF
– 75.00% – 20736
AF00
–27648
9400
100.000%
–27649
93FF
–117.593% –32512
8100
– 32513
80FF
117.596%
–32768
8000
118.519%
Table 5-11 Analog Value Representation in the Voltage Measuring Ranges 1 to 5 V and 0 to 10 V
System
Dec.
118.515% 32767
7FFF
117.593% 32512
7F00
117.589% 32511
7EFF
27649
6C01
100.000% 27648
6C00
75% 20736
5100
0.003617% 1
1
0% 0
0
–1
FFFF
– 17.593% –4864
ED00
– 4865
ECFF
v–17.596% –32768
8000
5-12
± 500 mV
± 250 mV
592.6 mV
296.3 mV
587.9 mV
294.0 mV
500 mV
250 mV
375 mV
187.54 mV
18.08 mV
9.04 mV
0 mV
0 mV
– 375 mV
–187.54 mV – 60 mV
– 500 mV
– 250 mV
– 587.9 mV
– 294.0 mV
– 592.6 mV
– 296.3 mV
Hex.
1 to 5 V
5.741 V
5.704 V
5 V
3.75 V
1 V + 144.7 mV
1 V
0.296 V
S7-400, M7-400 Programmable Controllers Module Specifications
Voltage Measuring Range
± 80 mV
± 50 mV
94.8 mV
59.3 mV
29.6 mV
94.1 mV
58.8 mV
29.4 mV
80 mV
50 mV
25 mV
60 mV
37.5 mV
18.75 mV
2.89 mV
1.81 mV
904.2 nV
0 mV
0 mV
0 mV
– 37.5 mV
– 18.75 mV
– 80 mV
– 50 mV
– 25 mV
– 94.1 mV
– 58.8 mV
– 29.4 mV
– 94.8 mV
– 59.3 mV
– 29.6 mV
Voltage Measuring Range
0 to 10 V
11.852 V
11.759 V
10 V
7.5 V
0 V + 361.7 mV
0 V
Negative values not
g
possible
ibl
± 25 mV
Overflow
Overrange
Rated range
Underrange
Underflow
Overflow
Overrange
Rated range
Underrange
Underflow