Suppression of Interference, Limits of Error
Interference voltage suppression for f = nx (f1 "1%),
(f1 = interference frequency) n = 1, 2, ...
Common-mode
interference
)
(U
< 120 V
CM
ss
Series-mode interference
(peak value of interference
< rated value of input
range)
Crosstalk between the inputs
Operational limit (in the entire temperature range, with
reference to the input range)
Voltage input
" 25 mV
" 50 mV
" 80 mV
" 250 mV
" 500 mV
" 1 V
" 2.5 V
" 5 V
1 V to 5 V
" 10 V
Current input
0 mA to 20 mA
" 5 mA
" 10 mA
" 20 mA
4 mA to 20 mA
Resistance test
0 to 48 W;
four-conductor
measurement
0 to 150 W,
four-conductor
measurement
0 to 300 W,
four-conductor
measurement
0 to 600 W;
four-conductor
measurement
0 to 5000 W;
four-conductor
measurement (in
the range of
6000 W)
0 to 300 W;
three-conductor
measurement
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
> 100 dB
> 40 dB
> 70 dB
" 0.35 %
" 0.32%
" 0.31%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.3%
" 0.4%
0 to 600 W;
three-conductor
measurement
0 to 5000 Ω;
three-conductor
measurement (in
the range of
6000 W)
Thermocouples
TC type B
TC type R
TC type S
TC type T
TC type E
TC type J
TC type K
TC type U
TC type L
TC type N
Resistance thermocouples, four-conductor
standard measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
Climatic measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
Resistance thermocouples, three-conductor
standard measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
Climatic measuring range
Pt 100
Pt 200
Pt 500
Pt 1000
Ni 100
Ni 1000
Analog Modules
" 0.4%
" 0.4%
" 11.5 K
" 7.3 K
" 8.3 K
" 1.7 K
" 3.2 K
" 4.3 K
" 6.2 K
" 2.8 K
" 4.2 K
" 4.4 K
" 3.1 K
" 4.9 K
" 3.9 K
" 3.1 K
" 0.8 K
" 0.8 K
" 0.4 K
" 0.4 K
" 0.4 K
" 0.4 K
" 0.8 K
" 0.8 K
" 4.2 K
" 6.5 K
" 5.2 K
" 4.2 K
" 1.0 K
" 1.0 K
" 0.5 K
" 0.5 K
" 0.5 K
" 0.5 K
" 1.0 K
" 1.0 K
5-111