Siemens Simatic M7-400 Reference Manual page 589

Programmable controllers module specifications
Hide thumbs Also See for Simatic M7-400:
Table of Contents

Advertisement

Bytes 4 to 8 of the SM 431; AI 16
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Figure B-18
Bytes 9 to 24 of the SM 431; AI 16 x 16 Bit
Data record 1 with bytes 9 to 24 contains the channel-specific diagnostic data. The
figure below shows the assignment of the diagnostic byte for a channel of the
module.
Figure B-19
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
16 Bit
7 6
5 4 3 2 1
0
0
Channel type B#16#71: analog input
7
0
7
0
7 6
5 4 3 2 1
0
Channel error, channel 0
Channel error, channel 1
...
Channel error, channel 6
Channel error, channel 7
7 6
5 4 3 2 1
0
...
Channel error, channel 9
Channel error, channel 14
Channel error, channel 15
Bytes 4 to 8 of the Diagnostic Data of the SM 431; AI 16 x 16 Bit
7 6
5 4 3 2 1
0
0
0
Configuring/parameter assignment error
Short-circuit to M
Wire break
Reference channel error
Underflow
Overflow
Diagnostic Byte for a Channel of the SM 431; AI 16 x 16 Bit
Diagnostic Data of the Signal Modules
Number of diagnostics bits that the module
outputs per channel: 8 bits long
Number of channels of the same
type in one module: 16 channels
Channel error, channel 8
B-15