Table 15: Error Messages (Error Byte) - Siemens SIMATIC NET CP 243-1 Technical Manual

Communications processor for industrial ethernet
Hide thumbs Also See for SIMATIC NET CP 243-1:
Table of Contents

Advertisement

09/02
Error byte
hex
dec
16#84 132
A command with an unallowable
data block number was started.

Table 15: Error messages (error byte)

Error word
hex
dec
16#0001
1
Timeout on the S7 bus
16#000D
13
All data transmissions were
aborted because a reconfigura-
tion was initiated by the user
program.
16#0030
48
The configuration could not be
called up from the CPU within a
specified time period.
16#0031
49
A syntactically correct CDB
configuration was not found in
the S7-200 CPU memory.
16#0032
50
The CRC checksum of the con-
figuration data (CDB, NDB) is
incorrect.
16#0033
51
The configuration data for the
CP 243-1 are faulty or incor-
rectly stored.
16#0034
52
The pointer to the CDB is faulty
or no CDB is loaded.
CP 243-1
J31069-D0428-U001-A1-7618
Description
Description
Reaction / remedy
A new read/write command can
be initiated
The user program should be
checked
Reaction / troubleshooting
Automatic warm start
Restart of the system
Automatic warm start
Ensure that the ETHx_CTRL
subroutine is called up at the
beginning of the user pro-
grams.
Check the CDB pointer (byte
offset 46 in the SM memory
area)
Diagnostics
Return
mechanism
Byte
Return
offset
value
in SM
(ETHx_)
area
_XFR
Return mecha-
nism
Byte
Return
value
offset
in SM
(ETHx_)
area
20,21
_CTRL
20,21
_CTRL
20,21
_CTRL
20,21
_CTRL
20,21
_CTRL
20,21
_CTRL
20,21
_CTRL
63