Digital Modules
Technical Specifications of the
Dimensions and Weight
Dimensions W
H
D
(in millimeters)
Weight
Data for Specific Module
Number of inputs
Length of cable
•
Unshielded
•
Shielded
Voltages, Currents, Potentials
Power rated voltage of the
electronics L+
Number of inputs that can be
triggered simultaneously
Isolation
•
Between channels and
backplane bus
•
Between the channels
Permitted potential difference
•
Between the different
circuits
Insulation tested with
•
Channels against
backplane bus and load
voltage L+
Current consumption
•
From the backplane bus
Power dissipation of the
module
4-22
SM 421; DI 32 x 24 VDC
25
290
210
Status display
Approx. 500 g
Interrupts
Diagnostic functions
32
Substitute value can be applied
Max. 600 m
Input voltage
•
Max. 1000 m
•
•
Not required
Input current
•
32
Input delay
•
Yes
•
Input characteristic curve
No
Connection of two-wire BEROs
•
75 VDC / 60 VAC
500 VDC
Max. 20 mA
Typ. 6 W
S7-400, M7-400 Programmable Controllers Module Specifications
Status, Interrupts, Diagnostics
Green LED per
channel
None
None
No
Data for Selecting a Sensor
Rated value
24 VDC
For signal "1"
13 V to 30 V
For signal "0"
-30 V to 5 V
At signal "1"
7 mA
At "0" to "1"
1.2 ms to 4.8 ms
At "1" to "0"
1.2 ms to 4.8 ms
To IEC 61131; type 1
Possible
Permitted bias current
Max. 1.5 mA
A5E00069467-07