Digital Modules
Technical Specifications of the
Dimensions and Weight
Dimensions W
H
D
(in millimeters)
Weight
Data for Specific Module
Number of inputs
Length of cable
Unshielded
Shielded
Voltages, Currents, Potentials
Power rated voltage of the
electronics L+
Number of inputs that can be
triggered simultaneously
Isolation
Between channels and
backplane bus
Between the channels
Permitted potential difference
Between the different
circuits
Insulation tested with
Channels against
backplane bus and load
voltage L+
Current consumption
From the backplane bus
Power dissipation of the
module
4-22
SM 421; DI 32 x 24 VDC
25
290
210
Status display
Approx. 500 g
Interrupts
Diagnostic functions
32
Substitute value can be applied
Max. 600 m
Input voltage
Max. 1000 m
Not required
Input current
32
Input delay
Yes
Input characteristic curve
No
Connection of two-wire BEROs
75 VDC / 60 VAC
500 VDC
Max. 20 mA
Typ. 6 W
S7-400, M7-400 Programmable Controllers Module Specifications
Status, Interrupts, Diagnostics
Green LED per
channel
None
None
No
Data for Selecting a Sensor
Rated value
24 VDC
For signal "1"
13 V to 30 V
For signal "0"
-30 V to 5 V
At signal "1"
7 mA
At "0" to "1"
1.2 ms to 4.8 ms
At "1" to "0"
1.2 ms to 4.8 ms
To IEC 61131; type 1
Possible
Permitted bias current
Max. 1.5 mA