Switches; S600 Main Board Reset; S601 Reset Status Led Switch; S602 Ground Fault Supervision Switch - Siemens PAD-5 Series Installation Manual

Intelligent notification and auxiliary power expander
Table of Contents

Advertisement

Model PAD-5
1
3.2.6
3.2.6.1
Button
Function
S600
Reset main microprocessor
on main board
3.2.6.2
Button
Function
Switch resets current state of
S601
Aux and NAC LEDs
3.2.6.3
Button
Function
S602
Enables/Disables Ground
Fault Detection
NOTE→ To comply with UL 864 the Ground Fault Detection must NOT be disabled
3.3
Supply input
Battery output
34
Siemens Industry, Inc.
Smart Infrastructure

Switches

S600 Main Board RESET

Position
Not pressed
Pressed

S601 Reset Status LED switch

Position
Not pressed
Pressed

S602 Ground Fault Supervision Switch

Position
EN
DIS

Technical Data

Plug strip
Operating Voltage
Operating current (standby)
Max. operating current.
Input current (active)
Design
Plug strip
Voltage
Current
Meaning
Normal
Resets only the main microprocessor on the
periphery board.
Meaning
Previous state of NACs and Aux circuits
Steady: In Trouble
Blinking: Was in Trouble (Currently Normal)
Clears previous state and reports current
state of NACs and Aux circuits
Meaning
Normal – Ground Fault Detection Enabled
Ground Fault Detection Disabled
X100
DC 26 V nominal, filtered
63 mA
9.1 A
FP2011-U1 (for batteries < 35 Ah) Rated:
6A Max @ 24 VDC
FP2012-U1 (for batteries 35 Ah and larger)
Rated: 9A Max @ 24 VDC
Not power limited
X101
DC 20.4 V...DC 26.4 V
(DC 24 V nominal)
Max. 11.5 A
A6V101030358_en--_c