PROFIBUS DP Master Interface IM 467/IM 467 FO
8.4

Technical Specifications

8.4.1
Technical Specifications of the IM 467
6ES7467-5GJ02-0AB0.
Dimensions and Weight
Dimensions
W x H x D (mm)
Weight
PROFIBUS DP
Standard
Transmission rate
Transmission
technology
Current consumption
Current consumption from
the S7-400 bus (24 VDC)
The IM does not consume
any current at 24 V, and it
only makes this voltage
available at the MPI/DP
interface.
8-12
25 x 290 x 210
700 g
PROFIBUS DP,
EN 50 170
9.6 kbps to 12 Mbps,
parameterizable in steps
RS 485 via 9-pin
subminiature D female
connector
Total current consumption
of the components
connected to the DP
interfaces, with a maximum
of 150 mA
S7-400, M7-400 Programmable Controllers Module Specifications
PROFIBUS DP
Conditions of Use
Can be used in
SIMATIC S7-400, max. 4
IM 467 in the central
controller
IM 467 cannot be used together with the CP 443-5
Supply voltage
5 VDC via the backplane
bus
Current consumption
1.3 A
From 5 VDC
Addressing range
Max. 4 KB for inputs and 4
KB for outputs
DP master
Yes
DPV 1
No
Enable/disable
No
Number of connectable I/O
96
devices
(slaves)
Number of connections for
32 + 1 diagnostic
S7 functions for the
connection
programming device and
operation and monitoring
Data volume per slave
Max. 244 bytes
Consistency
Max. 128 bytes
Configuration software
STEP 7
DP slave
No
Deviations from the DP Interface Integrated
in the CPU
Different SSL IDs for system diagnostics
Possibly extended SFC run times
Additional return codes for SFC 14 and
SFC 15