Parameter Sets for Signal Modules
A.1
How to Assign the Parameters for Signal Modules in
the User Program
Parameter Assignment in the User Program
You have already assigned parameters to the modules in STEP 7.
In the user program, you can use a SFC:
• to reassign parameters to the module and
• and transfer the parameters from the CPU to the addressed signal module
In the M7-400
In M7-400 programmable controllers you can also parameterize the signal modules
in the user program with the M7 API software (refer to System Software Manuals
for M7-300/400).
Parameters Stored in Data Records
The signal module parameters are stored in data records 0 and 1.
Modifiable Parameters
You can change the parameters of record 1 and pass them to the signal module
using SFC 55. The parameters set on the CPU are not changed when you do this!
You cannot modify the parameters of data record 0 in the user program.
SFCs for Parameter Assignment
The following SFCs are available for assigning parameters to the signal modules in
the user program:
Table A-1
SFCs for assigning Parameters to Signal Modules
SFC No.
55
WR_PARM
56
WR_DPARM
57
PARM_MOD
A-2
Identifier
Transfer of modifiable parameters (data record 1) to the
addressed signal module.
Transfer of parameters (data record 0 or 1) from the CPU
to the addressed signal module.
Transfer of all parameters (data record 0 and 1) from the
CPU to the addressed signal module.
S7-400, M7-400 Programmable Controllers Module Specifications
Application
A5E00069467-07