Digital Modules
Technical Specifications of the SM 421; DI 32
Dimensions and Weight
Dimensions W
H
D (mm)
Weight
Data for Specific Module
Number of inputs
Length of cable
Unshielded
Shielded
Voltages, Currents, Potentials
Rated load voltage L+
Reverse polarity protection
Number of inputs that can be
triggered simultaneously
Isolation
Between channels and
backplane bus
Between the channels
In groups of
Permitted potential difference
Between M
and the
internal
inputs
Between the inputs of the
different groups
Insulation tested with
Current consumption
From the backplane bus
Power dissipation of the
module
Status, Interrupts, Diagnostics
Status display
Interrupts
Diagnostic functions
4-58
25
290
210
Input voltage
Approx. 600 g
32
Input current
600 m
1000 m
Input delay
79 to 132 VAC
80 to 132 VDC
Yes
Input characteristic curve
32
Connection of two-wire BEROs
Yes
Yes
8
120 VAC
250 VAC
1500 VAC
Max. 0.2 A
Typ. 6.5 W
Green LED per
channel
None
None
S7-400, M7-400 Programmable Controllers Module Specifications
120 VUC
Data for Selecting a Sensor
Rated value
120 VUC
For signal "1"
79 to 132 VAC
80 VDC to 132 VDC
For signal "0"
0 to 20 V
Frequency range
47 to 63 Hz
At signal "1"
2 mA to 5 mA
At signal "0"
0 to 1 mA
At "0" to "1"
5 to 25 ms
At "1" to "0"
5 to 25 ms
To IEC 61131; type 1
Possible
Permitted bias current
Max.1 mA