Siemens Simatic M7-400 Reference Manual page 350

Programmable controllers module specifications
Hide thumbs Also See for Simatic M7-400:
Table of Contents

Advertisement

Analog Modules
Operational limit (in the entire temperature range, with
reference to the input range)
Voltage input
Current input
Thermocouple
Basic error (operational limit at 25 _C, referred to input
range)
Voltage input
Current input
Thermocouple
Temperature error (with
reference to the input
range)
Linearity error (with
reference to the input
range)
Repeatability (in steady
state at 25 _C, with
reference to the input
range)
5-134
" 0.3 %
" 0.5 %
" 3.5 _C
Type B
" 2.7 _C
Type N
" 1.8 _C
Type E
" 3.3 _C
Type R
" 3.2 _C
Type S
" 2.4 _C
Type J
" 1.7 _C
Type L
" 0.8 _C
Type T
" 2.5 _C
Type K
" 1.2 _C
Type U
" 0.05 %
" 0.15 %
" 0.9 _C
Type B
" 0.7 _C
Type N
" 0.5 _C
Type E
" 0.9 _C
Type R
" 0.8 _C
Type S
" 0.6 _C
Type J
" 0.4 _C
Type L
" 0.2 _C
Type T
" 0.6 _C
Type K
" 0.3 _C
Type U
" 0.015%/K
" 0.15%
" 0.15%
S7-400, M7-400 Programmable Controllers Module Specifications
Status, Interrupts, Diagnostics
Interrupts
Hardware interrupt
Diagnostic Interrupt
Diagnostic functions
Group error display
For internal fault
For external fault
Diagnostic information
can be displayed
Data for Selecting a Sensor
Input range (rated
values)/Input resistance
Voltage
Current
Thermocouple
Maximum input voltage for
voltage input (destruction
limit)
Maximum input current for
current input (destruction
limit)
Connection of the sensor
For measuring voltage
For measuring current
As four-wire transmitter
Characteristic linearization
For thermocouples
Temperature compensation
Internal temperature
compensation
Unit for temperature
measurement
Parameters can be
assigned
Programmable
Programmable
Programmable
Red LED (INTF)
Red LED (EXTF)
Yes
" 25 mV
>2 MΩ
" 50 mV
>2 MΩ
" 80 mV
>2 MΩ
"100 mV
>2 MΩ
"250 mV
>2 MΩ
"500 mV
>2 MΩ
" 1 V
>2 MΩ
" 2.5 V
>2 MΩ
" 5 V
>2 MΩ
" 10 V
>2 MΩ
" 25 mA
/50 Ω
Types B, N,
>2 MΩ
E, R, S, J, L,
T, K, U
35 V continuous;
75 V for max. 1 s
(duty factor 1:20)
32 mA
Possible
Possible
Types B, N, E, R, S, J, L,
T, K, U
Yes, programmable
Possible
Degrees Celsius; degrees
Fahrenheit
A5E00069467-07

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-400S7-400M7-400