Specifications
Enclosure
A1
A2
A3
A4
A5
B1
B2
B3
B4
C1
C2
C3
C4
Table 10.13 380-480 V, Frame Sizes A, B and C
10
10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
74
Power [kW]
Recommended
fuse size
-
gG-10
1.1-4.0
gG-10 (0.37-3)
gG-16 (4)
5.5-7.5
gG-16
1.1-4.0
gG-10 (0.37-3)
gG-16 (4)
1.1-7.5
gG-10 (0.37-3)
gG-16 (4-7.5)
11-18.5
gG-40
22-30
gG-50 (18.5)
gG-63 (22)
11-18
gG-40
22-37
gG-50 (18.5)
gG-63 (22)
gG-80 (30)
37-55
gG-80 (30)
gG-100 (37)
gG-160 (45)
75-90
aR-200 (55)
aR-250 (75)
45-55
gG-100 (37)
gG-160 (45)
75-90
aR-200 (55)
aR-250 (75)
MG20M902 - VLT
®
VLT
AQUA Drive
Operating Instructions
Recommended
Max. fuse
gG-25
gG-25
gG-32
gG-32
gG-32
gG-80
gG-100
gG-63
gG-125
gG-160
aR-250
gG-150 (37)
gG-160 (45)
aR-250
®
is a registered Danfoss trademark
Recommended circuit
Max trip level [A]
breaker
Moeller
PKZM0-16
PKZM0-25
PKZM0-25
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
NZMB2-A250
16
25
25
25
25
63
100
50
100
160
250
150
250
Need help?
Do you have a question about the VLT AQUA Drive FC 202 and is the answer not in the manual?
Questions and answers