10.2 General Technical Data
Protection and Features
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches 95
°C ± 5 °C. An overload temperature cannot be reset until the temperature of the heatsink is below 70 °C ± 5 °C
(Guideline - these temperatures may vary for different power sizes, enclosures etc.). VLT
derating function to avoid it's heatsink reaching 95 °C.
•
The frequency converter is protected against short-circuits on motor terminals U, V, W.
•
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or too high.
•
The frequency converter is protected against earth faults on motor terminals U, V, W.
Mains supply (L1, L2, L3)
Supply voltage
Supply voltage
Supply voltage
Supply voltage
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage.
Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated
supply voltage.
Supply frequency
The frequency converter power supply is tested in accordance with IEC61000-4-28, 50 Hz +4/-6%.
10
10
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cosφ) near unity
Switching on input supply L1, L2, L3 (power-ups) ≤ enclosure type A
Switching on input supply L1, L2, L3 (power-ups) ≥ enclosure type B, C
Switching on input supply L1, L2, L3 (power-ups) ≥ enclosure type D, E, F
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480/600/690
V maximum.
Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
*
Dependent on power size.
Torque characteristics
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
*Percentage relates to VLT AQUA Drive's nominal torque.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
68
®
VLT
AQUA Drive
Operating Instructions
®
MG20M902 - VLT
is a registered Danfoss trademark
®
AQUA Drive has an auto
200-240 V ±10%
380-480 V ±10%
525-600 V ±10%
525-690 V ±10%
50/60 Hz +4/-6%
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
maximum 2 times/min.
maximum 1 time/min.
maximum 1 time/2 min.
overvoltage category III/pollution degree 2
0-100% of supply voltage
maximum 110% for 1 min.
maximum 135% up to 0.5 s
maximum 110% for 1 min.
(> 0.98)
*
0-590 Hz
Unlimited
1-3600 s
*
*
*