Chapter 6

Understanding UPS Operation

6.1

UPS System Overview

The Power Xpert 9395 UPS is a continuous-duty, solid-state, transformerless (at 480 Vac), three-phase, true
online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical
load.
The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel,
integrated communication server, and digital signal processor (DSP) logic. Figure 6-1 shows the main elements
of the UPS system.
If utility power is interrupted or falls outside the parameters specified in Chapter 10, "Product Specifications"
the UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or
until the utility power returns. For extended power outages, the UPS allows you to either transfer to an
alternative power system (such as a generator) or shut down your critical load in an orderly manner.
AC Input to
Rectifier/
Charger
AC Input to
Bypass
NOTE On a UPS configured as an Input Output Module (IOM), the bypass input, static switch, bypass breaker (CB4), and
backfeed protection contactor (K5) are not present.
NOTE On a UPS configured with a Continuous Static Switch (CSS), bypass breaker (CB4) is not present.

Figure 6-1. Main Elements of the UPS System

The emergency bypass consists of a continuous static switch, and a backfeed protection contactor K5. The
bypass breaker (if installed) is located in parallel with the static switch. The backfeed protection contactor is
located in series with the static switch. The static switch is armed and ready during normal operation.
Power Xpert
Battery System
Input
Breaker
Input
CB1
Contactor
(optional)
K1
Rectifier
TM
9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10 www.eaton.com/powerquality
Battery
Battery
Breaker
Battery
Contactor
K2
Battery
Converter
Inverter
Power Module
Digital
Metering
Backfeed
Protection
Contactor
K5
Static
Switch
Bypass Breaker (CB4)
UPS Cabinet
Output
Contactor
K3
AC Output
to Critical
Load
6-1