Eaton
Power Xpert
9395C UPS
1000kW/1000kVA, 1000kW/1100kVA or 1100kW/1100kVA
Installation and Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Eaton Power Xpert Series

  • Page 1 ® ® Eaton Power Xpert 9395C UPS 1000kW/1000kVA, 1000kW/1100kVA or 1100kW/1100kVA Installation and Operation Manual...
  • Page 3 ® ® Eaton Power Xpert 9395C UPS 1000kW/1000kVA, 1000kW/1100kVA or 1100kW/1100kVA Installation and Operation Manual...
  • Page 4 National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ©Copyright 2018 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 5: Table Of Contents

    4.11 Completing the Installation Checklist ............4-34 ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 6 Using the Remote Emergency Power-off Switch ........7-28 ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 7 WARRANTY....................® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 8 TABLE OF CONTENTS This page intentionally left blank. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 9 Eaton 9395C-1100 UPS ........
  • Page 10 Figure 7-39. ESS Comparison Screen ..............7-25 ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 11 PM Section Air Filter Locations ............® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 12 LIST OF FIGURES This page intentionally left blank. ® ® viii Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 13: Introduction

    The Power Xpert 9395C contains a section configured as an integrated system bypass module (ISBM) rated for a maximum of 1100 kVA. The Eaton 9395C online power protection system is used to prevent loss of valuable electronic information, minimize equipment downtime, and minimize the adverse effect on production equipment due to unexpected power problems.
  • Page 14: Ups Standard Features

    Some system configurations may limit the number of inputs available. The UPS uses these inputs to monitor the building alarms in addition to the UPS status. See Chapter 8, “Communication” for additional information. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 15: Advanced Battery Management

    1.2.2 Sync Control An optional Eaton 9395C Sync Control maintains the critical load outputs of two separate single module 9395C UPS systems in synchronization. This option facilitates the uninterrupted transfer of the load from one load bus to another by means of transfer switches. The Sync Control is housed in a wall-mounted panel that can be located between the UPS units for easy wiring.
  • Page 16: Battery System

    See the battery related documents located in the system manual for battery cabinet specifics. Using This Manual This manual describes how to install and operate the Eaton 9395C UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation. In particular, be thoroughly familiar with the REPO procedure (see paragraph 7.4.2).
  • Page 17: Conventions Used In This Manual

    This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 18: Getting Help

    All other countries: Call your local service representative Please use the following e-mail address for manual comments, suggestions, or to report an error in this manual: E-ESSDocumentation@eaton.com ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 19: Safety Warnings

    (ground) connection with loads attached. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 20 The operating environment should be maintained within the parameters stated in this manual. Keep surroundings uncluttered, clean, and free from excess moisture. Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 21 End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling. If these instructions are not followed, damage to the wiring channel and wiring will occur. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 22 Si ces instructions ne sont pas suivies, des dommages au câblage et à son canal surviendront. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 23 Section I Installation...
  • Page 25: Ups Installation Plan And Unpacking

    If the UPS is to be operated at an altitude higher than 1000m (3300 ft), contact an Eaton service representative for important information about high altitude operation. The operating environment must meet the weight, clearance, and environmental requirements specified.
  • Page 26: Installation Considerations

    When ignored, either one of these aspects can create an undesirable microclimate at the UPS location. If the environment created by this microclimate exceeds the Eaton 9395C-1100 UPS operating specification, the UPS reliability, over time, will be reduced. These same environmental extremes will also create reliability concerns for any servers that are exposed to them.
  • Page 27: Figure 3-1. Ups Cabinet Dimensions - (Front View)

    UPS Installation Plan and Unpacking NOTE Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental requirements supersede the UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton's Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more information.
  • Page 28: Figure 3-2. Ups Cabinet Dimensions (Right Side View)

    UPS Installation Plan and Unpacking 38.8 [32.7] [1.5] Dimensions are in millimeters [inches]. [34.2] Figure 3-2. UPS Cabinet Dimensions (Right Side View) ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 29: Figure 3-3. Isbm Section Dimensions (Front View)

    Dimensions are in millimeters [inches]. Figure 3-3. ISBM Section Dimensions (Front View) [1.3] [18.5] [TBD] [TBD] Front Dimensions are in millimeters [inches]. Figure 3-4. ISBM Section Dimensions (Top View) ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 30: Figure 3-5. Isbm Section Dimensions (Bottom View)

    UPS Installation Plan and Unpacking Figure 3-5. ISBM Section Dimensions (Bottom View) 1964 [77.3] 2223 [87.5] Dimensions are in millimeters [inches]. Figure 3-6. PM Section Dimensions ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 31: Figure 3-7. Pm Dimensions - (Top View)

    UPS Installation Plan and Unpacking 2192.6 [86.3] 720.7 720.8 720.7 [28.37] [28.38] [28.37] Dimensions are in millimeters [inches]. Front Figure 3-7. PM Dimensions – (Top View) ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 32: Figure 3-8. Ups Center Of Gravity

    CENTER OF GRAVITY 1964 [77.3] 1160 [45.7] 453 [17.8] 416 [16.4] 1220 [48.1] ISBM 470 [18.5] 1132 [44.6] POWER CABINET Side View Figure 3-8. UPS Center of Gravity ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 33: Ups System Power Wiring Preparation

    (from a Wye source) for proper equipment operation. The Eaton 9395C 480V unit is designed for operation on a grounded-wye source of supply. There is no additional connection point for a neutral conductor. The output of this UPS will not directly support phase to neutral loads.
  • Page 34 NOTE Callout letters , and map to Figure 6-5. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 35 Terminals E1 through E11 are 2-hole busbar mountings for standard NEMA 2-hole barrel lugs. The power wiring connections for this equipment a Table 3-9 for recommended installation parts and tools not supplied by Eaton. Figure 4-15 through Figure 4-17 show the location of the power cable terminals inside the UPS.
  • Page 36 Rectifier Input, Bypass Input, Conical Washer 180500037-120 Battery Input, and Output Rectifier Input, Bypass Input, 180200001-07 Battery Input, and Output Table 3-9. Recommended Installation Parts and Tools (Not Supplied by Eaton) Part Size Quantity Manufacturer Part Number Notes 2/0 AWG Thomas &...
  • Page 37 External overcurrent protection and disconnect are not provided by this product, but are required by codes. Refer to Table 3-4 for wiring requirements. If an output lockable disconnect is required, it is to be supplied by the customer. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 3-13...
  • Page 38 Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at 2 volts per cell. ® ® 3-14 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 39 The building alarms can be programmed to display the alarm functional name. LAN drops for use with X-Slot connectivity cards must be provided by the customer and may need to use Class 1 wiring, see above. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 3-15...
  • Page 40: Inspecting And Unpacking The Ups Cabinets

    DO NOT angle fork tips upward. Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the cabinet. ® ® 3-16 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 41 Si ces instructions ne sont pas suivies, des dommages au câblage et à son canal surviendront. Carefully inspect the outer packaging for evidence of damage during transit. CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. ATTENTION! Ne pas installer une armoire endommagée.
  • Page 42 Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact an Eaton service representative immediately to determine the extent of the damage and its impact on further installation.
  • Page 43: Figure 3-10. Ups Cabinet As Shipped On Pallet (Isbm Section)

    UPS Installation Plan and Unpacking Figure 3-10. UPS Cabinet as Shipped on Pallet (ISBM Section) ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 3-19...
  • Page 44: Figure 3-11. Ups Cabinet As Shipped On Pallet (Pm Section)

    UPS Installation Plan and Unpacking Figure 3-11. UPS Cabinet as Shipped on Pallet (PM Section) ® ® 3-20 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 45: Installation

    éviter de renverser les armoires, ce qui pourrait causer de graves blessures. CAUTION Do not tilt cabinets more than 10° from vertical. Lift the cabinets only with a forklift or damage may occur. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 46 ISBM and PM section center of gravity measurements). If the sections must be moved using the cabinet front or rear fork lift slots, see the caution statements at the beginning of this procedure. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 47: Figure 4-1. Removing The Isbm Section Left Side Shipping Bracket

    (see Figure 4-2 or Figure 4-6). Remove the right side shipping bracket. Front Door Shipping Bracket Pallet Bolts Shipping Bracket Left Side Shipping Bolts Bracket Figure 4-1. Removing the ISBM Section Left Side Shipping Bracket ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 48: Figure 4-2. Removing The Isbm Section Right Side Shipping Bracket

    Pull the pallet from under the cabinet. Discard or recycle the pallet and shipping brackets in a responsible manner. Carefully lower the cabinet until the cabinet base contacts the floor. Repeat Steps 2 through 6 for the remaining cabinet. Proceed to paragraph 4-5. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 49: Figure 4-3. Removing The Pm Section Left Side Shipping Bracket

    Installation Removable Front Panels Pallet Shipping Bracket Bolts Shipping Bracket Left Side Shipping Bolts Bracket Figure 4-3. Removing the PM Section Left Side Shipping Bracket ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 50: Figure 4-4. Removing The Pm Section Right Side Shipping Bracket

    Installation Pallet Shipping Bracket Bolts Right Side Shipping Bracket Shipping Bracket Bolts Figure 4-4. Removing the PM Section Right Side Shipping Bracket ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 51: Mechanically Joining The Sections

    Use care during installation to protect components mounted on the right side of the ISBM section and the intercabinet wiring harnesses attached to the left side PM section from damage. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 52: Figure 4-6. Isbm And Pm Sections Joined

    Align the holes in the flat brackets over holes in the top rear and top front of the ISBM and PM sections. Secure the brackets with the screws from the hardware kit (see Figure 4-7). ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 53: Electrically Connecting The Sections

    AC and DC input intercabinet power wiring harnesses are supplied coiled and secured in the ISBM wireway on the right side of the ISBM section (see Figure 4-6). ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 54 11. Connect the ground braid to the PM section ground bolt and secure. NOTE Intercabinet interface wiring harnesses are supplied coiled inside the protective cage on the right side panel of the ISBM section (see Figure 4-10). ® ® 4-10 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 55 20. Dress the interface harnesses and secure in place with wire ties as necessary to prevent wire damage. 21. When all wiring is complete, reinstall the safety shield panels removed in previous steps. 22. Reinstall the front wireway panel. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 4-11...
  • Page 56: Figure 4-8. Isbm Section Intercabinet Power Terminal Locations

    PM Fan Panel Power Module (PM) (Left door panel removed) Ground lug location (Behind fan panel) Figure 4-8. ISBM Section Intercabinet Power Terminal Locations ® ® 4-12 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 57: Figure 4-9. Isbm Section Output Power To Pm Terminal Detail

    PM Cable Power Out Yellow (2) Output PM Cable Power Out Yellow PM Cable Power Out Yellow Figure 4-9. ISBM Section Output Power to PM Terminal Detail ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 4-13...
  • Page 58: Figure 4-10. Ups Intercabinet Interface Harness Locations

    ISBM to PM AC Wiring Access PM Ground Cable Access ISBM Section Right Side View PM Section Left Side View Figure 4-10. UPS Intercabinet Interface Harness Locations ® ® 4-14 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 59: Figure 4-11. Pl1 Interface Board Location

    ISBM Section Right Side Inside View Figure 4-11. Pl1 Interface Board Location Pl1 Interface Board J39 to Power Module CAN Connector Figure 4-12. J39 Location on Pl1 Interface Board ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 4-15...
  • Page 60: Battery System Installation

    ISBM section. Install the conduit plate and install all conduit runs into the plate. Pull wiring through conduit into the ISBM section wiring area. ® ® 4-16 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 61: Figure 4-13. Isbm And Pm Section Debris Shields

    Installation ISBM Top Debris Shields PM Top Figure 4-13. ISBM and PM Section Debris Shields ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 4-17...
  • Page 62: Figure 4-14. Isbm And Pm Section Conduit And Wire Entry Locations

    Input and Output, and DC Input (Remove panel to drill or punch conduit holes.) Figure 4-14. ISBM and PM Section Conduit and Wire Entry Locations ® ® 4-18 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 63 Using hardware from the external wiring terminal hardware kit (see Table 3-8), connect phase A, B, and C power wiring from output terminals to the critical load. See paragraph 3.2.3 for wiring and termination requirements. Proceed to paragraph 4.6.2. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 4-19...
  • Page 64: Figure 4-15. Isbm Section Power Terminal Locations

    (See Figure 4‐19 or Figure 4‐20 for Detail BB.) Phase A (E9) AC Output Phase B (E10) Critical Load Phase C (E11) ISBM Figure 4-15. ISBM Section Power Terminal Locations ® ® 4-20 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 65: Figure 4-16. Isbm Section Power Terminal Detail Aa

    (E8) AC INPUT (E6) TO BYPASS E1/E2/E3 (E1) (E7) AC INPUT (E2) TO RECTIFIER (E3) SECTION A-A Figure 4-16. ISBM Section Power Terminal Detail AA ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 4-21...
  • Page 66: Battery Power Wiring

    Se reporter au chapitre 10 sur les notices techniques pour connaître les tensions maximales du chargeur de batteries.Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et communiquer avec un représentant du service Eaton immédiatement. To install wiring to connections:...
  • Page 67: Installing Interface Connections

    Hazardous voltages are present near the user interface terminal area if the UPS is not totally disconnected. AVERTISSEMENT! Des tensions dangereuses sont présentes près de l’enceinte du terminal de l’interface utilisateur si l’onduleur n’est pas totalement débranché. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 4-23...
  • Page 68: Tb1, Tb2, And Tb3 Connections (Other Than Tb1 Battery Interface Connections)

    10. Reinstall the top internal safety shield panel and secure with the retained hardware. 11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. Close the door and secure the latch. ® ® 4-24 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 69: Figure 4-18. Isbm Section Interface Terminal Locations

    X-Slot Communication Bays (See Figure 4‐21 (See Figure 4‐25 for detail.) for detail.) (See Figure 4‐24 for terminal assignments.) ISBM Figure 4-18. ISBM Section Interface Terminal Locations. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 4-25...
  • Page 70 Building Alarm 5 Return NOTE “Return“ indicates connection to electronics circuit ground. “Common” indicates connection to common side of isolated relay contact. ® ® 4-26 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 71: Figure 4-19. Interface Terminal Detail

    NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of 22 AWG. Figure 4-20. Typical Alarm Relay Connection ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 4-27...
  • Page 72: Figure 4-21. Terminal Blocks Tb1, Tb2, And Tb3 Connector Assignments

    NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used. Figure 4-21. Terminal Blocks TB1, TB2, and TB3 Connector Assignments ® ® 4-28 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 73: Tb1 Battery Interface Connections

    The UPS requires a battery breaker(s) with +48VDC UVR(s). UVR circuit is fused at 1 amp and can support up to twelve Eaton battery cabinets with UVRs. The unit must be pre-charged before the customer can close the battery breaker(s).
  • Page 74: X-Slot Connections

    When installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communication bay. For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10). To install wiring to connections: If not already installed, install the LAN drops.
  • Page 75: Installing A Repo Switch

    The REPO switch must be a normally-open or normally-closed latching-type switch not tied into any other circuits. NOTE This procedure is intended to be used for the installation of the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure only as a guide.
  • Page 76: Figure 4-25. Normally-Open Repo Switch Wiring

    13. Reinstall the top internal safety shield panel and secure with the retained hardware. 14. Reinstall the front door removed in Step 4 and secure with the retained hardware. 15. Close the door and secure the latch. ® ® 4-32 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 77: Figure 4-26. Normally-Closed Repo Switch Wiring

    NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Figure 4-27. Normally-Closed and Normally-Open REPO Switch Wiring ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 4-33...
  • Page 78: Installing Options, Accessories, And Distributed Bypass Control Wiring

    W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 79 Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) The debris shields covering the UPS cabinet ventilation grills are removed. Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. ®...
  • Page 80 Installation Checklist Notes ® ® 4-36 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 81 Hot Sync CAN Bridge card (see paragraph 5.1) Parallel system wiring (see paragraph 5.2) RMP II (see paragraph 5.2) RIM II (see paragraph 5.3) SCM II (see paragraph 5.4) ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 82: Figure 5-1. Powerware Hot Sync Can Bridge Card

    UPS. See Figure 4-18 and Figure 4-23 for X-Slot communication bay locations. To locate the appropriate terminals on the Powerware Hot Sync CAN Bridge Card, see Figure 5-2 and Table 5-1. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 83: Figure 5-2. Hot Sync Can Bridge Card Connections

    Normally-open contact closes when UPS is on bypass. RMP II, RIM II, and SCM II connections. CAN L Can H CAN input for parallel operation. Shield ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 84 Close the front door and secure the latch. 10. Restart the UPS. See Chapter 7, “UPS Operating Instructions” for startup instructions ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 85: Figure 5-3. Remote Monitor Panel Ii And Relay Interface Module Ii Terminal Locations

    TB1–5 (RDX*) 0.9 (8) Use twisted pair J3–7 (TX) TB1–4 (RDX) 0.9 (8) TB3 Line 0.9 (8) TB3 Neutral 0.9 (8) Ground Terminal 2.7 (24) Maximum ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 86 If all connections are secure but the RMP II continues to self-test, replace the fuse with the spare included in the hardware kit. If a fuse replacement does not correct the problem, contact an Eaton service representative for verification that the RMP II is working correctly.
  • Page 87: Figure 5-5. J1, J2, J3, And J4 15-Pin D-Sub Connector

    Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 11. Contact an Eaton service representative for verification and testing of the RIM II and its connections prior to making connections with J1 through J4 (see Table 5-3 and Figure 5-5).
  • Page 88: Figure 5-6. Supervisory Contact Module Ii Terminal Location

    120 Vac Power Ground Terminal Terminal TB2 Customer Supervisory Contact Interface Terminal TB1 Signal Connections from the UPS Figure 5-6. Supervisory Contact Module II Terminal Location ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 89: Figure 5-7. Supervisory Contact Module Ii Tb2

    NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. Install wiring between the SCM II terminal block TB2 and the monitoring equipment. See Figure 5-6 for terminal block location and Figure 5-7 for terminal assignments.
  • Page 90: Figure 5-8. Remote Monitor Panel Ii Dimensions

    Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5-8. Remote Monitor Panel II Dimensions ® ® 5-10 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 91: Figure 5-9. Relay Interface Module Ii Dimensions

    Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5-9. Relay Interface Module II Dimensions ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 5-11...
  • Page 92: Figure 5-10. Supervisory Contact Module Ii Dimensions

    Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5-10. Supervisory Contact Module II Dimensions ® ® 5-12 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 93 Section II Operation...
  • Page 95: Figure 6-1. Main Elements Of The Ups System

    Chapter 6 Understanding UPS Operation UPS System Overview The Eaton Power Xpert 9395C-1100 UPS is a continuous-duty, solid-state, transformerless (at 480 Vac), three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
  • Page 96 The inverter produces a three-phase AC output to a customer's load without the use of a transformer. The inverter derives regulated DC from the rectifier and uses IGBT devices and pulse-width modulation (PWM) to produce a regulated and filtered AC output. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 97: Figure 6-2. Path Of Current Through The Ups In Online Mode

    ESS mode is a normal operating mode, and not an alarm condition. While the UPS is in this mode, the Online light on the front display will illuminate. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 98 Les charges critiques ne sont pas protégées des fluctuations de tension ou de fréquence ni des pannes de courant lorsque l’onduleur est en mode Contournement. The Eaton 9395C UPS provides backfeed detection and protection through a shunt trip mechanism of the bypass input breaker.
  • Page 99: Figure 6-3. Path Of Current Through The Ups In Bypass Mode

    Converter Main Power Flow Breakers Contactors Trickle Current Closed Battery Breaker Energized Open De-Energized Battery Figure 6-4. Path of Current Through the UPS in Battery Mode ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 100 Key K-ML must be inserted in the Load Bank breaker lock of the system to be connected to the load bank. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 101 Key K-ML must be inserted in the Load Bank breaker lock of the system to be connected to the load bank. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 102 Single Reverse Transfer UPS – Two PM, Common Rectifier Feed, Common Battery, Dual-Feed Figure 6-5 on page 6-9 Eaton 9395C Configuration Figure 6-6 on page 6-10 Eaton 9395C Simplified Dual-Feed UPS with Maintenance Bypass Panel ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 103: Figure 6-5. One Pm, Common Rectifier Feed, Common Battery, Dual-Feed Configuration

    NOTE Backfeed protection is not provided as a part of UPS. Customer supplied bypass input breaker with 48-60 VDC shunt trip is required. Figure 6-5. One PM, Common Rectifier Feed, Common Battery, Dual-Feed Configuration ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 104: Figure 6-6. Simplified Dual-Feed Ups With Maintenance Bypass Panel

    (BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass. Figure 6-6. Simplified Dual-Feed UPS with Maintenance Bypass Panel ® ® 6-10 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 105: Figure 7-1. Ups Controls And Indicators

    The control panel is used to set up and control the UPS, and to monitor UPS operation. For a description of the UPS control panel functions, see paragraph 7.3. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 106: Figure 7-2. Remote Shunt Trip Switch - Front View

    Red and green lamps indicate breaker status (Red = Closed, Green = Open). A center-mounted pushbutton switch remotely shunt trips the DC breaker. Figure 7-2. Remote Shunt Trip Switch - Front View ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 107: Figure 7-3. Ups Color Touchscreen Control Panel (Typical)

    For a description of the UPS control panel functions, see paragraph 7.3. Color Touchscreen Control Panel ISBM Figure 7-3. UPS Color Touchscreen Control Panel (Typical) ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 108: Figure 7-4. Ups Color Touchscreen Control Panel (Typical)

    When the unit powers up, the screen displays as shown in Figure 7-4. When power is applied to the system, the display advances to the Sign In screen shown in Figure 7-5. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 109: Figure 7-5. Parts Of The Touch Screen

    (see Figure 7-6). Figure 7-5. Parts of the Touch Screen ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 110: Figure 7-6. Sign In Or Password Request Screen

    The UPS status area automatically displays the Eaton model number, current time and date, active alarms, active notices, and load percent and battery run time for the UPS. If the Eaton Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed. The small head symbol between the system model and time allows the operator select a different language from an imbedded list.
  • Page 111: Figure 7-7. Home Screen

    Yellow lines indicates an out-of-tolerance condition. NOTE Screens shown are representative examples of system operation. The screen data will vary based on system activity at the time of observation. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 112: Figure 7-8. Main Menu And Power Maps Screen (Online Mode)

    Figure 7-8. Main Menu and Power Maps Screen (Online Mode) Touching the LOAD kVA button displays the Output kVA screen shown in Figure 7-9. Figure 7-9. Output kVA Screen from Home Screen ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 113: Figure 7-10. Average Efficiency Screen From Home Screen

    Figure 7-10. Average Efficiency Screen from Home Screen Touching the CONSUMPTION button displays the screen shown in Figure 7-11. Figure 7-11. Consumption Screen from Home Screen ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 114: Figure 7-12. Bypass Screen

    Figure 7-13 is an example of a command request confirmation pop-up screen. This type of pop-up allows the user to confirm that the requested command is valid. Figure 7-13. Typical Command Confirmation Screen (Charger Off) ® ® 7-10 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 115: Figure 7-14. Meters Summary Screen

    Figure 7‐10 Figure 7‐10 Figure 7‐10 ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ Figure 7‐11 Figu Figure 7‐11 Figure 7-14. Meters Summary Screen ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 7-11...
  • Page 116: Figure 7-15. Input Meters Screen

    Figure 7-15. Input Meters Screen The Bypass Meters Screen shown in Figure 7-16 displays values pertaining to the Bypass conditions. Figure 7-16. Bypass Meters Screen ® ® 7-12 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 117: Figure 7-17. Output Meters Screen

    UPS Operating Instructions The Output Meters Screen shown in Figure 7-17 displays values pertaining to the system output. Figure 7-17. Output Meters Screen ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 7-13...
  • Page 118: Figure 7-18. Input Meters Detail Screen

    Figure 7-18. Input Meters Detail Screen The Select Source screen shown in Figure 7-19 allows the operator to choose the individual source for system readings. Figure 7-19. Select Source Screen ® ® 7-14 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 119: Figure 7-20. Battery Meters Screen

    Figure 7-20 shows the Battery Meters basic screen. Figure 7-21 shows the Battery Log access screen. Figure 7-20. Battery Meters Screen Figure 7-21. Battery Log Screen ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 7-15...
  • Page 120: Figure 7-22. Battery Log Detail

    Figure 7-22 shows the Battery Log Detail screen. Figure 7-23 shows the Battery Log Summary screen. Figure 7-22. Battery Log Detail Figure 7-23. Battery Log Summary Screen ® ® 7-16 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 121: Figure 7-24. System Events Screen

    This message is also written to the Active Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 7-17...
  • Page 122: Figure 7-25. User Log Screen

    Selecting an event opens the Event Detail screen shown in Figure 7-26. This screen details the specifics of the event for the user to see. Figure 7-26. User Log Detail Screen ® ® 7-18 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 123: Figure 7-27. System Status Screen

    Figure 7-28 shows the Module Controls screen. This screen allows control of the individual modules within the system. It also gives their values and status. Figure 7-28. Module Controls Screen ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 7-19...
  • Page 124: Figure 7-29. Module Control Detail Screen

    The Metering Method screen allows the operator to select line-to-line or line-to-neutral monitoring values. See Figure 7-30 or Figure 7-31. Figure 7-30. Online Mode Metering Method Option Screen ® ® 7-20 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 125: Figure 7-31. Bypass Mode Metering Method Option Screen

    Touching the CLEAN SCREEN button disables the screen for 30 seconds to allow the user to safely clean the screen without affecting operation. Figure 7-32. Settings Screen ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 7-21...
  • Page 126: Figure 7-33. Configuration Options Screen

    The various Energy Advantage Architecture operations are described in the UPS Installation and Operation manual for your system. Figure 7-34. Energy Advantage Architecture (EAA) Screen ® ® 7-22 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 127: Figure 7-35. Disable Ess Screen

    Figure 7-36. High Alert Timer Screen This screen shown in Figure 7-36 asks the operator if they want to start the High Alert mode timer. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 7-23...
  • Page 128: Figure 7-37. Statistics Basic Screen

    The screen shown in Figure 7-37 allows the operator to query the system for various operational statistics such as shown in Figure 7-38. Figure 7-37. Statistics Basic Screen Figure 7-38. Statistics Data Detail Screen ® ® 7-24 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 129: Figure 7-39. Ess Comparison Screen

    Figure 7-39. ESS Comparison Screen 7.3.19 UPS Module Map Screen The screen shown Figure 7-40 allows the operator to control the individual UPM(s). Figure 7-40. UPS Module Map Screen ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 7-25...
  • Page 130: Figure 7-41. System Overview Screen

    UPS Operating Instructions 7.3.20 System Overview Screen The screen shown Figure 7-41 displays values for all UPS and UPM parameters. Figure 7-41. System Overview Screen ® ® 7-26 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 131 UPS and create a personnel hazard. Note that all battery cabinets provided by the UPS manufacturer have this circuit breaker as a standard feature. 11. Close the battery breaker. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 7-27...
  • Page 132 à l’étape suivante. N’utiliser cette fonction que pour mettre la charge critique hors tension. NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 133: Figure 7-42. Repo Operation

    L ’intérieur de l’armoire de l’onduleur est alimenté jusqu’à ce que le disjoncteur du circuit d’alimentation en amont soit activé. Activated Deactivated Pushbutton locked into place Unlock pushbutton to release Figure 7-42. REPO Operation ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 7-29...
  • Page 134 UPS Operating Instructions This page intentionally left blank. ® ® 7-30 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 135: Figure 8-1. Optional X-Slot Cards

    LAN drops for use with X-Slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10). Refer to the manual supplied with the X-Slot card for user instructions.
  • Page 136 Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
  • Page 137 Manager for UPS management and monitoring, and Intelligent Power® Protector, which allows graceful shutdown of operating systems. Eaton’s Intelligent Power Software gives you all the tools you need to monitor and manage power devices on your network, even in a virtualized environment. This innovative software solution combines the most critical applications in ensuring system uptime and data integrity: not only power monitoring and management, but also graceful shutdown during an extended power outage.
  • Page 138: Figure 8-2. Remote Monitor Panel Ii

    The RMP II can be flush-mounted or surface-mounted on a desktop, or secured to a wall. Figure 8-2 shows an RMP II. Figure 8-2. Remote Monitor Panel II ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 139 The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This indicator is accompanied by a horn. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 140: Figure 8-3. Relay Interface Module Ii

    Contacts are closed when approximately two minutes of battery time is remaining before the BATTERY WEAK Pins 5 and 14 critical load is lost. UTILITY FAILURE Pins 6 and 15 Contacts are closed when Utility Failure is detected. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 141: Figure 8-4. Supervisory Contact Module Ii

    BYPASS NOT AVAILABLE TB2-10 through TB2-12 ON BATTERY TB2-13 through TB2-15 UPS ALARM TB2-16 through TB2-18 ON BYPASS TB2-19 through TB2-21 SHUTDOWN IMMINENT TB2-22 through TB2-24 ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 142 Communication This page intentionally left blank. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 143 THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. If the string requires service, refer to the battery manufacturer's operating manual for instructions on battery maintenance or contact an Eaton service representative.
  • Page 144 Check the UPS air filters (located behind the front panels or door) and wash or replace as necessary. See Figure 9-1 and Figure 9-2 for filter locations, and Table 9-1 for filter sizes. Contact an Eaton service representative for replacement filters. To remove and replace the filters: Table 9-1.
  • Page 145 Reinstall the ISBM section front panel removed in Step b. and secure with the retained hardware. If opened, close the front door and secure the latch. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 146: Figure 9-1. Isbm Section Air Filter Locations - Continuous Static Switch

    UPS Maintenance Middle ISBM Air Filter Bottom ISBM Air Filters Figure 9-1. ISBM Section Air Filter Locations - Continuous Static Switch ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 147: Figure 9-2. Pm Section Air Filter Locations

    9.2.4 ANNUAL Maintenance Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings. 9.2.5 BATTERY Maintenance Contact an Eaton service representative for battery maintenance.
  • Page 148 Ne pas éliminer les déchets d’équipements électriques et électroniques (DEEE) aux ordures. Pour connaître la méthode d’élimination appropriée, communiquer avec le centre régional de récupération/réutilisation ou d’élimination des déchets dangereux. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 149 UPS Maintenance Maintenance Training A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Eaton Help Desk (see page 1-6).
  • Page 150 UPS Maintenance This page intentionally left blank. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 151 Battery Voltage 48 Vdc Up to 480A with less than 85% load Battery Charging Capacity Up to 80A with 100% load Battery UVR 320 Vdc ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality 10-1...
  • Page 152 10.2.4 Battery RunTime Ratings Battery Ambient Runtime Temperature (minutes) 1100 1100 35°C (95°F) 1100 1000 40°C (104°F) 1000 1000 40°C (104°F) NOTE Timer will be disabled below 700kW ® ® 10-2 Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 153 Eaton-built battery cabinets, (individually and collectively, the “Warranted Items”) are free from defects in material and workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton's sole obligation will be to repair or replace such defective item (including by providing service, parts and labor, as applicable), at the option of Eaton.
  • Page 154 This page intentionally left blank. ® ® Eaton Power Xpert 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality...
  • Page 156 *P-164000821 1* P-164000821 1...