Festo P.BE−VIFB5−03−EN en 0503e
Formula for cable length:
− 21.6 V) · A ·
(V
Bmin
v
L
2  I

This means:
21.6 V V
VALVE TERMINAL
V
= minimum supply voltage
Bmin
(at the power unit)
l
= current for electronics and inputs
1
I
= current for outputs/valves
2
A = cable cross−sectional area (uniform e. g. 1.5 mm
κ = conductance value of cables
κ
(uniform e. g.
Cu
Example:
I
=
1 A
1
I
=
5 A
2
V
=
24 V
Bmin
V
= 21.6 V
VALVE TERMINALmin
κ
=
56
Cu
Result of example:
L v 18 m for A = 1.5 mm
L v 30 m for A = 2.5 mm
κ
CU
+ I
2
1
= 24 V ± 10%, minimum: w 21.6 V
m
= 56
2
· Ω
mm
m
2
mm
· ≅ Ω
2
2
2
)