Water Drainage - COMBITHERM CT PROformance Series Installation Manual

Table of Contents

Advertisement

w A T e r d r A I N A g e - f O r S I N g L e O v e N
A union is required. Install a 1-1/2-inch (40mm) diameter connection, drain line and clamp into place.
The drain line must always be a positive gradient away from the Combitherm oven. An end of drain run
air gap may be required by local code. Vertical air vent required.
NOTICE: In the U.S.A., this equipment is to be installed to comply with the Basic Plumbing Code of the
Building Officials and Code Administrators International, Inc. [BOCA], and the Food Service
Sanitation Manual of the Food & Drug Administration [FDA].
Example Installation
with Plumbing Kit #5018195 (Gas)
or Plumbing Kit #5018612 (Electric)
Kits have a maximum run length of
4-1/2' (1372mm)
COMBITHERM CT PROFORMANCE AND CT CLASSIC SERIES • INSTALLATION MANUAL • MN-35947 • 50.
INSTALLATION
WARNING:
To prevent SERIOUS INJURY or PROPERTY DAMAGE
from slippery floor conditions, check drain is connected
properly and not blocked.
Drain
Connection
1-1/2" (40mm)
1-1/2" (40mm) diameter pipe
To Drain - Floor Sink
with Positive Descending Slope
Drain materials must
withstand temperatures
up to 200°F (93°C).
If a drain run exceeds 6' (1829mm)
to the floor sink, an air gap is
strongly recommended.
Drain vent pipe must be above
oven exhaust vent opening!
Oven exhaust vent opening
45 Degree Elbow
1-1/2" (40mm) diameter CPVC
Tee Fitting Drain Connection
45 Degree Elbow