Service Conditions; Accessories; Further Information - AUMA SA 07.2 Operation Instructions Manual

Multi-turn actuator; control unit: electromechanic with actuator controls
Hide thumbs Also See for SA 07.2:
Table of Contents

Advertisement

SA 07.2
SA 16.2/SAR 07.2
AC 01.2 Intrusive
12.3

Service conditions

Use
Mounting position
Enclosure protection according
to EN 60529
Corrosion protection
Installation altitude
Humidity
Pollution degree
Finish coating
Colour
Ambient temperature
Vibration resistance according
to IEC 60068-2-6
Lifetime
Weight
12.4

Accessories

1)
Wall bracket
Programming software for PC
1)
Cable length between actuator and AUMATIC max. 100 m. Not suitable for version with potentiometer in the actuator. Instead of the
potentiometer, an RWG has to be used.
12.5

Further information

EU Directives
SAR 16.2 Control unit: electromechanic
Indoor and outdoor use permissible
Any position
Standard: IP 68 with AUMA 3-ph AC motor/1-ph AC motor
According to AUMA definition, enclosure protection IP 68 meets the following requirements:
Depth of water: maximum 8 m head of water
Duration of continuous immersion in water: max. 96 hours
Up to 10 operations during flooding.
Modulating duty is not possible during continuous immersion.
For actual version, refer to actuator/controls name plate.
Standard:
KS: Suitable for installation in industrial units, in water or power plants with a low pollutant
concentration as well as for installation in occasionally or permanently aggressive atmo-
sphere with a moderate pollutant concentration (e.g. in wastewater treatment plants,
chemical industry)
Options:
KX: Suitable for installation in extremely aggressive atmospheres with high humidity and
high pollutant concentration
Standard: ≤ 2,000 m above sea level
Option: > 2,000 m above sea level, please contact AUMA
Up to 100 % relative humidity over the entire permissible temperature range
Pollution degree 4 (when closed) according to 50178
Standard: Paint based on polyurethane (powder coating)
Standard: AUMA silver-grey (similar to RAL 7037)
Standard:
Open-close duty: 25 °C to +70 °C
Modulating duty: 25 °C to +60 °C
For actual version, refer to actuator/controls name plate.
1 g, from 10 to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength
may not be derived from this. Not valid in combination with gearboxes.
AUMA part-turn actuators meet or exceed the lifetime requirements of EN 15714-2. For further
details, please contact AUMA
Refer to separate technical data
AUMATIC mounted separately from the actuator, including plug/socket connector. Connecting
cables on request. Recommended for high ambient temperatures, difficult access, or in case
of heavy vibration during service
AUMA ToolSuite
Electromagnetic Compatibility (EMC): (2004/108/EC)
Low Voltage Directive: (2006/95/EC)
Machinery Directive: (2006/42/EC)
Technical data
65