AUMA SA 07.2 Operation Instructions Manual page 63

Multi-turn actuator; control unit: electromechanic with actuator controls
Hide thumbs Also See for SA 07.2:
Table of Contents

Advertisement

SA 07.2
SA 16.2/SAR 07.2
AC 01.2 Intrusive
Status signals
Position feedback signal
Voltage output
Local controls
Bluetooth
Communication interface
Application functions
SAR 16.2 Control unit: electromechanic
Standard:
6 programmable output contacts:
5 potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive load)
Default configuration: End position CLOSED, end position OPEN, selector switch in
-
REMOTE, torque fault CLOSE, torque fault OPEN
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
-
Default configuration: Collective fault signal (torque fault, phase failure, motor protec-
tion tripped)
Options:
6 programmable output contacts:
5 change-over contacts with one common, max. 250 V AC, 5 A (resistive load)
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
12 programmable output contacts:
10 potential-free NO contacts, one common for respectively 5 contacts, max. 250 V AC,
1 A (resistive load)
2 potential-free change-over contacts, max. 250 V AC, 5 A (resistive load)
6 programmable output contacts:
6 potential-free change-over contacts without one common, per contact max. 250 V AC,
5 A (resistive load)
10 programmable output contacts:
10 potential-free change-over contacts without one common, per contact max. 250 V
AC, 5 A (resistive load)
All output signals must be supplied with the same potential.
Galvanically isolated analogue output E2 = 0/4
Standard:
Auxiliary voltage 24 V DC, max. 100 mA for supply of the control inputs, galvanically isolated
from internal voltage supply
Option:
Auxiliary voltage 115 V AC, max. 30 mA to supply the control inputs
from internal voltage supply
Standard:
Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
Push buttons OPEN, STOP, CLOSE, RESET
6 indication lights:
End position CLOSED (yellow), torque fault CLOSE (red), motor protection tripped
-
(red), torque fault OPEN (red), end position and running indication OPEN (green),
Bluetooth (blue)
Graphic LC display, illuminated
Options:
Special colours for the 5 indication lights:
-
End position CLOSED (green), torque fault CLOSE (blue), torque fault OPEN (yellow),
motor protection tripped (white), end position OPEN (red)
Bluetooth class II chip, version 2.0 with a range up to 10 m in industrial environments. Supports
the SPP Bluetooth profile (Serial Port Profile).
Programming software:
AUMA ToolSuite, commissioning and diagnostic tool for windows based PCs, PDAs and
smart phones
Standard:
Switch-off mode adjustable
-
Limit or torque seating for end position OPEN and end position CLOSED
Torque by-pass, adjustable up to 5 seconds (no torque monitoring during this time)
Start and end of stepping mode as well as ON and OFF time (1 up to 1,800 seconds)
can be programmed individually for directions OPEN and CLOSE.
Any 8 intermediate positions between 0 and 100 %, reaction and signal behaviour pro-
grammable
Options:
Positioner
Position setpoint via analogue input E1 = 0/4
-
-
Automatic adaptation of the dead band (adaptive behaviour can be selected)
-
Split Range operation
-
MODE input for selecting between OPEN - CLOSE duty and modulating duty
4)
4)
20 mA (load max. 500 Ω)
20 mA
Technical data
5)
, galvanically isolated
63